Electrical Installation – System-Electrical Information

UPS ratings 220 V

10 kVA

15 kVA

20kVA

30 kVA

8 kW

12 kW

16 kW

24 kW

 

 

 

 

 

 

Input voltage / Bypass voltage (V)

3-phase

3-phase

3-phase

3-phase

 

220Y/

220Y/

220Y/

220Y/

 

127 V

127 V

127 V

127 V

 

 

 

 

 

Input current (nominal, per phase) (A)

22.9

34.6

46.5

68.9

 

 

 

 

 

Maximum input current per phase (continuous, at

25.2

38.0

50.1

75.8

minimum mains voltage)

 

 

 

 

 

 

 

 

 

Input current protection for mains source or single

3x35

3x60

3x80

3x125

mains supply (external to UPS, not supplied) (A)

 

 

 

 

 

 

 

 

 

Input current protection for bypass source in dual mains

35

60

80

125

configuration (external to UPS, not supplied) (A)

 

 

 

 

 

 

 

 

 

Input frequency (Hz) range

40-70

40-70

40-70

40-70

 

 

 

 

 

Output voltage (on line). (V)

127/220

127/220

127/220

127/220

Minimum and maximum values (+/- 1%)

 

 

 

 

 

 

 

 

 

Output current (nominal, per phase) (A)

26.2

39.4

52.5

78.7

 

 

 

 

 

Maximum output current

28.9

43.3

57.7

86.6

(in bypass only at 110% overload per phase)

 

 

 

 

 

 

 

 

 

Neutral output current (with 100% switch mode load)

45.5

68.2

90.9

136.4

(A)

 

 

 

 

 

 

 

 

 

Output current protection (external to UPS, not

40

60

80

120

supplied) (A)

 

 

 

 

 

 

 

 

 

Output frequency range (Hz)

50/60

50/60

50/60

50/60

 

 

 

 

 

DC overcurrent protection and disconnect switch for

26.4

39.6

52.7

78.9

external safety:

 

 

 

 

DC voltage rating of the battery supply

+/- 192

+/- 192

+/- 192

+/- 192

Maximum available short-circuit current

10 kA

10 kA

10 kA

10 kA

 

 

 

 

 

990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

23

Page 29
Image 29
American Power Conversion 208/220 installation manual UPS ratings 220