Operator

Interface

System Mode Overrides

Description

Resolution or (Enumerations), Default

Units

Monitor Value

 

1. Compressor

XXX / (Auto,Manual [0-100] ), Auto

Enum

IGV % Open

 

 

Control Signal

 

 

Evap. LWT

 

 

 

 

 

AFD Freq.

 

2. Evap Water Pump

(Auto, On), Auto

Enum

1) Evap Flow

 

 

 

 

 

status

 

 

 

 

 

2) Override Tim

 

 

 

 

 

e Remaining

 

3. Cond Water Pump

(Auto, On), Auto

Enum

1) Cond Flow

 

 

 

 

 

status

 

 

 

 

 

2) Override Time

 

 

 

 

 

Remaining

 

Circuit Mode Overrides

 

 

 

 

Description

Resolution or (Enumerations), Default

Units

Monitor Value

 

1. Oil Pump

(Auto, On), Auto

Enum

1) Diff press

 

 

 

 

 

2) Override Time

 

 

 

 

 

Remaining

 

2. Clear Restart Inhibit Timer

 

 

 

 

3. Purge Exhaust Circuit Test

(Off, On), Off

Enum

none

 

4. Purge Regen Cycle

(Off, On), Off

Enum

Carbon Temp

 

5. Front Panel Ckt Lockout

(Not Locked Out, Locked Out), Not Locked Out

Enum

 

 

Purge

 

 

 

 

 

Description

Resolution or (Enumerations), Default

Units

 

 

 

1. Purge Operating Mode

(Auto, On, Adaptive, Stop), Adaptive

Enum

 

 

 

2. Daily Pumpout Limit

XXX

Minutes

 

 

 

3. Disable Daily Pumpout Limit

 

 

 

 

 

(0 to disable)

0, XX

Hours

 

 

 

4. Purge Liquid Temp Inhibit

(Enable, Disable), Enable

Enum

 

 

 

5. Purge Liquid Temp Limit

XXX.X

Temperature

 

 

Display Settings

 

 

 

 

Description

Resolution or (Enumerations), Default

 

Units

 

1. Date Format

(“mmm dd, yyy”, “dd-mmm-yyyy”), “mmm dd, yyy”

Enum

 

2. Date

 

 

 

 

3. Time Format

(12-hour, 24-hour), 12-hour

 

Enum

 

4. Time of Day

 

 

 

 

5. Keypad/Display Lockout

(Enable, Disable), Disable

 

Enum

 

6. Display Units

(SI, English), English

 

Enum

 

7. Pressure Units

(Gauge, Absolute), Absolute

 

Enum

 

8. Language

(English, Selection 2, Selection 3), English (2)

Enum

 

(1)Temperatures will be adjustable to 0.1 degree F or C. The Main Processor provides the minimum and maximum allowable value.

(2)Adjustable to the nearest whole number percent. The Main Processor provides the minimum and maximum allowable value.

(3)Terminates with 10 minutes if inactivity

(4)The Date and Time setup screen formats deviate slightly from the standard screens defined above. See the time and date section for further details.

(5)Enables a DynaViewLockout screen. All other screens timeout in 30 minutes to this screen when enabled. The DynaViewLockout Screen displays a 0-9 keypad to permit the user to exit the lockout with a fixed password (1-5-9 + Enter). See lockout setion for further details.

(6)Language choices are dependent on what has been setup in the Main Processor. Language selections will include English and qty 2 alternate as loaded by TechView. Language shall always be the last setting listed on the Display Settings menu. This will allow a user to find language selection if looking at an unrecognizable language.

(7)Manual Compressor Control allows an operator to override the Auto Control and manually control the compressor while in operation. This is not active during Stop mode.

CDHF-SVU01C-EN

45

Page 45
Image 45