Operator
Interface
System Mode Overrides
Description | Resolution or (Enumerations), Default | Units | Monitor Value |
| |
1. Compressor | XXX / (Auto,Manual | Enum | IGV % Open |
| |
| Control Signal |
|
| Evap. LWT |
|
|
|
|
| AFD Freq. |
|
2. Evap Water Pump | (Auto, On), Auto | Enum | 1) Evap Flow |
| |
|
|
|
| status |
|
|
|
|
| 2) Override Tim |
|
|
|
|
| e Remaining |
|
3. Cond Water Pump | (Auto, On), Auto | Enum | 1) Cond Flow |
| |
|
|
|
| status |
|
|
|
|
| 2) Override Time |
|
|
|
|
| Remaining |
|
Circuit Mode Overrides |
|
|
|
| |
Description | Resolution or (Enumerations), Default | Units | Monitor Value |
| |
1. Oil Pump | (Auto, On), Auto | Enum | 1) Diff press |
| |
|
|
|
| 2) Override Time |
|
|
|
|
| Remaining |
|
2. Clear Restart Inhibit Timer |
|
|
|
| |
3. Purge Exhaust Circuit Test | (Off, On), Off | Enum | none |
| |
4. Purge Regen Cycle | (Off, On), Off | Enum | Carbon Temp |
| |
5. Front Panel Ckt Lockout | (Not Locked Out, Locked Out), Not Locked Out | Enum |
| ||
| Purge |
|
|
|
|
| Description | Resolution or (Enumerations), Default | Units |
|
|
| 1. Purge Operating Mode | (Auto, On, Adaptive, Stop), Adaptive | Enum |
|
|
| 2. Daily Pumpout Limit | XXX | Minutes |
|
|
| 3. Disable Daily Pumpout Limit |
|
|
|
|
| (0 to disable) | 0, XX | Hours |
|
|
| 4. Purge Liquid Temp Inhibit | (Enable, Disable), Enable | Enum |
|
|
| 5. Purge Liquid Temp Limit | XXX.X | Temperature |
|
|
Display Settings |
|
|
|
| |
Description | Resolution or (Enumerations), Default |
| Units |
| |
1. Date Format | (“mmm dd, yyy”, | Enum |
| ||
2. Date |
|
|
|
| |
3. Time Format |
| Enum |
| ||
4. Time of Day |
|
|
|
| |
5. Keypad/Display Lockout | (Enable, Disable), Disable |
| Enum |
| |
6. Display Units | (SI, English), English |
| Enum |
| |
7. Pressure Units | (Gauge, Absolute), Absolute |
| Enum |
| |
8. Language | (English, Selection 2, Selection 3), English (2) | Enum |
|
(1)Temperatures will be adjustable to 0.1 degree F or C. The Main Processor provides the minimum and maximum allowable value.
(2)Adjustable to the nearest whole number percent. The Main Processor provides the minimum and maximum allowable value.
(3)Terminates with 10 minutes if inactivity
(4)The Date and Time setup screen formats deviate slightly from the standard screens defined above. See the time and date section for further details.
(5)Enables a DynaView™ Lockout screen. All other screens timeout in 30 minutes to this screen when enabled. The DynaView™ Lockout Screen displays a
(6)Language choices are dependent on what has been setup in the Main Processor. Language selections will include English and qty 2 alternate as loaded by TechView™. Language shall always be the last setting listed on the Display Settings menu. This will allow a user to find language selection if looking at an unrecognizable language.
(7)Manual Compressor Control allows an operator to override the Auto Control and manually control the compressor while in operation. This is not active during Stop mode.
45 |