Control System Components

External Chilled Water

Setpoint (ECWS)

The External Chilled Water Setpoint allows the chilled water setpoint to be changed from a remote location. The External Chilled Water Setpoint is found on 1A16 J2-5 to J2-6 (Ground). 2-10 vdc and 4-20 ma corresponds to a default 34°F to 65°F (-17.8 to 18.3°C) adjustable via service tool.

WPSR (WFC Water Pressure Sensing Option)

External Current Limit Setpoint

The External Current Limit is an option that allows the current limit setpoint to be changed from a remote location. The External Limit Setpoint is found on 1A16 J2-2 to J2-3 (ground), 2-10 vdc and 4-20 ma each correspond to a 40 to 100 percent RLA range. UCP limits the maximum ECLS to 100 percent.

Default 40 to 100%, adjustable via service tool.

1A21 Optional Dual

WPSR = WFC

Signal #1

Evaporator Differential

Not for field use

Analog Input or output

 

 

Water Pressure

 

Module

 

 

 

 

1A21 Optional Dual

WPSR = WFC

Signal #2

Condenser Differential

Not for field use

Analog Input or output

 

 

Water Pressure

 

Module

 

 

 

 

Module Characteristics

1A1, 1A2 Power Supply :

Unit Control Power Supply Module Converts 27 vac to 24 vdc.

Power Input Voltage: 23VRMS minimum, 27VRMS Nominal, 30VRMS maximum

Frequency: 50-60 Hz

Current: Full load 27 VAC – 4.30 A (RMS)

Inrush 27 VAC (RMS) ~ 30A (RMS)

Power Output: Class II Voltage 24 VDC, Rated Current 2.44 Amps.

Fused at 3 amps (FUS01513)

1A3, 1A5, 1A10 Dual Relay Output modules :

Relay #1 J2-1 NO, J2-2 NC, J2-3 common

Relay #2 J2 4 NO, J2-5 NC, J2-6 common

Relay Outputs at 120 VAC: 7.2 Amps resistive, 2.88 Amps pilot duty, 1/3 HP, 7.2 FLA at 240 VAC: 5 Amps general purpose, 14 - 26 AWG with a maximum of two 14 AWG.

Power, 24 +/- 10 percent VDC, 60 mA maximum, Trane IPC3 protocol. J1-1 +24VDC, J1-2 Ground, J1-3 COMM + J1-4 COMM -

1A4, 1A6 Dual High Voltage Binary input module:

Binary Input Signal #1 J2-1 to 2

Binary Input Signal #2 J3-1 to 2

High Voltage Binary Input: Off

Voltage: 0 to 40 VAC RMS , On

Voltage: 70 to 276 VAC RMS

Input is not polarity sensitive (Hot and neutral can be switched), Input impedance 130K to 280K ohms

14 - 26 AWG with a maximum of two

14 AWG

Power, 24 +/- 10 percent VDC, 20 mA maximum. Trane IPC3 protocol. J1-1 +24VDC, J1-2 Ground, J1-3 COMM +, J1-4 COMM -

1A7 High Power Output Module Relay contacts at 120 VAC:

16 amps resistive, 6.4 amps,pilot duty, 1 HP

J2-14-26 awg witha maximum of two 14 awg

J2-1 J2-2 no, J2-3 NC, J2-4 com

CDHF-SVU01C-EN

61

Page 61