Control System

Components

EXOP Extended Operation Option

The following modules (1A17, 1A18, and 1A19) are provide when this control package is specified.

1A5 Quad Relay

EXOP

Relay #4

Ice Building Relay

J2-10 NO, J2-11 NC,

Output module

 

 

 

J2-12 common

1A17 Optional Dual Analog

EXOP

Signal #1

External Base Loading

J2-1 Output #1,

Input/Output Module

 

 

Setpoint input

J2-3 Ground

1A17 Optional Dual Analog

EXOP

Signal #2

Refrigerant monitor inputs

J2-4 Output #2,

Input/Output Module

 

 

 

J2-6 Ground

1A18 Optional Dual LV

EXOP

Signal #1

External Base Loading

J2-1 Binary Input Signal #1,

Binary input module

 

 

Enable or Disable input, points

J2-2 Ground

1A18 Optional Dual LV

EXOP

Signal #2

External Hot Water Control

J2-3 Binary Input Signal #2,

Binary input module

 

 

Enable or Disable input

J2-4 Ground

1A19 Optional Dual LV

EXOP

Signal #1

Ice Building Control

J2-1 Binary Input Signal #1,

Binary input module

 

 

Enable or Disable input point

J2-2 Ground

Refrigerant Monitor Input 1A17

Analog type input 4-20ma input signal to the 1A17 J2-4 to J2-6 (ground). This represents 0-100 ppm.

56

CDHF-SVU01C-EN

Page 56
Image 56