Control System

Components

GBAS (Generic Building Automation System)

1A15 Optional Dual

GBAS

Signal #1

Percent RLA Compressor Output

J2-1 Output #1, J2-3 Ground

Analog Input/

 

 

 

 

output Module

 

 

 

 

1A16 Optional Dual

GBAS

Signal #1

External Current limit Setpoint

J2-2 Input #1, J2-3 Ground

Analog Input/

 

 

 

 

output Module

 

 

 

 

1A16 Optional Dual

GBAS

Signal #2

Chilled Water Reset input,

J2-5 Input #2, J2-6 Ground

Analog Input/

 

 

or External Chiller Water Setpoint

 

output Module

 

 

 

 

Percent RLA Output

2 to 10 Vdc corresponding to 0 to

120% RLA. With a resolution of 0.146%. The Percent RLA Output connections are on the terminals 1A15 –J2-1 (+) to J2-3 (Ground). The Percent RLA Output is polarity sensitive.

The following graph illustrates the output:

Figure 27. Voltage versus percent RLA

60

CDHF-SVU01C-EN

Page 60
Image 60
American Standard CH530 manual Gbas Generic Building Automation System, Percent RLA Output