General Information

Ice Machine Control

UCP provides a service level “Enable or Disable” menu entry for the Ice Building feature when the Ice Building option is installed. Ice Building can be entered from “Front Panel”, or if hardware is specified the UCP will accept either an isolated contact closure (1A19 Terminals J2-1 and J2-2 (Ground) ) or a remote communicated input (Tracer) to initiate the ice building mode where the unit runs fully loaded at all times. Ice building will be terminated either by opening the contact or based on entering evaporator fluid temperature. UCP will not permit the Ice Building mode to be entered again until the unit is switched to the Non-ice building mode and back into the ice building mode. It is not acceptable to reset the chilled water setpoint low to achieve a fully loaded compressor. When entering ice- building the compressor will be loaded at its maximum rate and when leaving ice building the compressor will be unloaded at its maximum rate. While loading and unloading the compressor, all surge detection will be ignored. While in the ice building mode, current limit setpoints less than the maximum will be ignored. Ice Building can be terminated by one of the following means:

1.Front panel disable.

2.Opening the external Ice. Contacts/ Remote communicated input (Tracer).

3.Satisfying an evaporator entering fluid temperature setpoint. (Default is 27°F)

4.Surging for 7 minutes at full open IGV.

Figure 18. Sequence of operation: ice making: running to ice making

Figure 19. Sequence of operation: ice making: stopped to ice to ice building complete

26

CDHF-SVU01C-EN

Page 26
Image 26
American Standard CH530 manual Ice Machine Control, Sequence of operation ice making running to ice making