Operator

Interface

Report name: System ASHRAE Chiller Log

Description

Resolution

Units

Dependencies

1. Current Time/Date

XX:XX mmm dd, yyyy

Date / Time

 

2. Chiller Mode:

 

Enum

 

3. Active Chilled Water Setpoint:

XXX.X

Temperature

 

4. Active Current Limit Setpoint:

XXX

% RLA

 

5. Refrigerant Type:

 

Enum

 

6. Refrigerant Monitor:

XXX.X

PPM

If option installed

7. Evap Entering Water Temp:

XXX.X

Temperature

 

8. Evap Leaving Water Temp:

XXX.X

Temperature

 

9. Evap Water Flow Switch Status:

 

Enum

If option not installed

10. Evap Differential Wtr Press:

XXX.X

Diff Pressure

If option installed

11. Approx Evap Water Flow:

XXX.X

GPM/LPM

If option installed

12. Approx Chiller Capacity:

XXXX

Capacity

If option installed

13. Cond Entering Water Temp:

XXX.X

Temperature

 

14. Cond Leaving Water Temp:

XXX.X

Temperature

 

15. Cond Water Flow Switch Status:

 

Enum

If option not installed

16. Cond Differential Wtr Press:

XXX.X

Pressure

 

17. Approx. Cond Water Flow:

XXXX

Flow

If option installed

Report name: Circuit ASHRAE Chiller Log

 

 

 

Description

Resolution

Units

Dependencies

1. Circuit Operating Mode:

 

Enum

 

2. Amps L1 L2 L3

XXXX

Amps

XXX.X if less than

 

 

 

1000 Amps

3. Volts AB BC CA

XXXX

Volts

 

4. Purge Daily Pumpout –24 Hrs:

XXX.X

Min

 

5. Purge Daily Pumpout Limit/Alarm

XXX.X

Min

 

6. Purge Pumpout - Life

XXXXXX.X

Min

 

7. Purge Operating Mode:

 

Enum

 

8. Purge Status:

 

Enum

 

9. Compressor Starts:

XXXX

Integer

 

10. Compressor Running Time:

XX:XX

Hours:Minute

 

11. Compressor Rfgt Discharge Temp:

XXX.X

Temperature

If option installed

12. Oil Pump Discharge Pressure:

XXX.X

Pressure

 

13. Oil Tank Pressure:

XXX.X

Pressure

 

14. Differential Oil Pressure:

XXX.X

Diff Pressure

 

15. Oil Tank Temp:

XXX.X

Temperature

 

16. Inboard Bearing Temp:

XXX.X

Temperature

If option installed

17. Outboard Bearing Temp:

XXX.X

Temperature

If option installed

18. Evap Sat Refrigerant Temp:

XXX.X

Temperature

 

19. Evap Rfgt Pressure:

XXX.X

Pressure

 

20. Evap Approach Temp:

XXX.X

Temperature

 

21. Cond Sat Rfgt Temp:

XXX.X

Temperature

 

22. Cond Rfgt Pressure:

XXX.X

Pressure

 

23. Condenser Approach Temp:

XXX.X

Temperature

 

Historic Diagnostics Log

 

 

 

1 to 20 Historic Diagnostics (main processor 2.0 and later)

42

CDHF-SVU01C-EN

Page 42
Image 42
American Standard CH530 manual Report name System Ashrae Chiller Log, Historic Diagnostics Log