CDHF-SVU01C-EN
28
Unit ControlPanel (UCP)

Control Panel Devices and Unit

Mounted Devices

Unit Control Panel (UCP)
Safety and operating controls are
housed in the unit control panel, the
starter panel and the purge control
panel. The UCP ‘s operator interface
and main processor is called the
DynaView (DV) and is located on
the UCP door. (See Operators
interface section for detailed
information)

Figure 20. Left control panel

The UCP houses several other
controls modules called panel
mounted LLID (Low Level Intelligent
Device), power supply, terminal
block, fuse, circuit breakers, and
transformer. The IPC (Interprocessor
communication) bus provides
communication between LLID’s and
the main processor. Unit mounted
devices are called frame mounted
LLID’s and can be temperature
sensors or pressure transducers,
vane actuator. These and other
functional switches provide analog
and binary inputs to the control
system.