Operator Interface

The active chilled water setpoint is the setpoint that is currently in use. It will be displayed to 0.1 degrees Fahrenheit or Celsius. Touching the double arrow to the left of the Active Chilled Water Setpoint will take the user to the active chilled water setpoint arbitration sub-screen.

The Active Chilled Water Setpoint the result of arbitration between the front panel, BAS, and external setpoints,

The chilled water reset status area in the right most column will display one of the following messages: Return, Constant Return, Outdoor, None

The left column text “Front Panel”, “BAS”, “External”, Chilled Water Reset, and “Active Chilled Water Setpoint” will always be present regardless of installation or enabling those optional items. In the second column “- - - -” will be shown if that option is Not Installed, otherwise the current setpoint from that source will be shown.

The “Back” button provides navigation back to the chiller screen.

38

CDHF-SVU01C-EN

Page 38
Image 38
American Standard CH530 manual Back button provides navigation back to the chiller screen