Control Sequence of Operation

Current passing through circuit breaker 1Q5 reaches 2 normally open parallel sets of contacts: those of refrigerant and oil pump relay (1A7- J2-5 to 1), and the 2K11 interlocking relay. Connected at module 1A7-J2-2 to 4.

Note: While the (1A7-J2-5 to 1) relay automatically is closed by the main processor 1A22 as a part of the start sequence. It can also be closed manually by changing the oil pump status to “ON” in the manual over ride mode menu of DynaView.

Closure of the (1A7-J2-5 to 1), or 2K11 contacts also allows current to pass through the coil of the refrigerant

pump starter relay (4K8), to the start windings of the refrigerant pump. When motor 4M3 first starts, current draw is high: This causes current sensing relay 4K8 to close its normally open contacts and pull in of pump Capacitor 4C1. Increasing motor speed and related decreasing current through the main winding and relay coil reduce the magnetic force and the armature “Drops out” to open the start contacts and disconnect the start windings and capacitor. Current now flows only to the Run windings of the oil pump motor or refrigerant and oil pump motor.

Maximum Acceleration

Timer Setting

by Starter Type

Wye-Delta

27 Seconds

Auto-Transformer

16

Primary Reactor

16

Across the Line

6

Solid State

15

AFD

30

CDHF-SVU01C-EN

71

Page 71
Image 71
American Standard CH530 manual Afd