Control Sequence of Operation
Current passing through circuit breaker 1Q5 reaches 2 normally open parallel sets of contacts: those of refrigerant and oil pump relay (1A7-
Note: While the
Closure of the
pump starter relay (4K8), to the start windings of the refrigerant pump. When motor 4M3 first starts, current draw is high: This causes current sensing relay 4K8 to close its normally open contacts and pull in of pump Capacitor 4C1. Increasing motor speed and related decreasing current through the main winding and relay coil reduce the magnetic force and the armature “Drops out” to open the start contacts and disconnect the start windings and capacitor. Current now flows only to the Run windings of the oil pump motor or refrigerant and oil pump motor.
Maximum Acceleration
Timer Setting
by Starter Type
27 Seconds | |
16 | |
Primary Reactor | 16 |
Across the Line | 6 |
Solid State | 15 |
AFD | 30 |