Appendices 103
Table C.1: CCM Appliance Enterprise Traps (Continued)
Trap | Description and Variable(s) | |
|
| |
SpcDeviceOffline | An SPC power control device is offline. | |
Variables: SPC device location name and CCM appliance port number | ||
| ||
|
| |
SpcDeviceOnline | An SPC power control device is online. | |
Variables: SPC device location name and CCM appliance port number | ||
| ||
|
| |
| The CCM appliance was unable to log in to the SPC device using the username | |
SpcLoginErr | configured in the appliance. | |
| Variables: SPC device location, CCM appliance port number and username | |
|
| |
| A command was issued to turn off an SPC device socket. | |
SpcSocketOff | Variables: username who issued the command, name of server attached to SPC | |
Command | device socket, SPC device location name, CCM appliance port number and SPC | |
| device socket number |
An SPC device has detected an off sense failure for a socket. This occurs when a
SpcSocketOffSenseFail socket should be in the off state, but is actually in the on state.
Variables: name of server attached to the SPC device socket, SPC device location name, CCM appliance port number and SPC device socket number
| A command was issued to turn on an SPC device socket. |
SpcSocketOn | Variables: username who issued the command, name of server attached to SPC |
Command | device socket, SPC device location name, CCM appliance port number and SPC |
| device socket number |
An SPC device has detected an on sense failure for a socket. This occurs when a
SpcSocketOnSenseFail socket should be in the on state, but is actually in the off state.
Variables: name of server attached to the SPC device socket, SPC device location name, CCM appliance port number and SPC device socket number
| A command was issued to reboot an SPC power control device socket. | |
SpcSocketReboot | Variables: username who issued the command, name of server attached to the SPC | |
Command | device socket, SPC device location name, CCM appliance port number and SPC | |
| device socket number | |
|
| |
| An SPC device socket has changed to the off state. | |
SpcStatusSocketOff | Variables: name of server attached to the SPC device socket, SPC device location | |
| name, CCM appliance port number and SPC device socket number | |
|
| |
| An SPC power control device socket has changed to the on state. | |
SpcStatusSocketOn | Variables: name of server attached to the SPC device socket, SPC device location | |
| name, CCM appliance port number and SPC device socket number | |
|
| |
SpcTotalLoadHigh | An SPC device has exceeded the maximum threshold for total load amperage. | |
Variables: SPC device location name and CCM appliance port number | ||
| ||
|
| |
SpcTotalLoadLow | The total load amperage on an SPC device has gone below the minimum threshold. | |
Variables: SPC device location name and CCM appliance port number | ||
| ||
|
|