5.1.5 Power on checks

If at any time the status display shows a digit and a flashing decimal point, this indicates that the NextMove ST has detected a fault - see section 6.

1.Turn on the Logic supply (if separate from the Drive supply).

2.Turn on the Drive supply.

3.After a brief test sequence, ( followed by ), the Status display should show the node

number, for example , the factory default. If the display is not lit then re-check the power supply connections. A green surface mount LED (D16) near the center of the control card should also be flashing once every two seconds. The NextMove ST is now ready to be configured using WorkBench v5.

Note: If the red LED (D4) near the center of the control card remains illuminated, then the supply voltage to the NextMove ST control card is too low. See section 6.2.2 for LED locations.

5-2 Operation

MN1921

Page 36