6.6.3 Overdamped response

6.6.3 Overdamped response

If the graph shows that the response is overdamped (it reaches the demand too slowly, as shown in Figure 30) then the value for KDERIV should be decreased to reduce the damping of the move. If the overdamping is excessive, it may be necessary to increase the value of

KPROP.

Demand position

Measured position

Figure 30 - Overdamped response

10.Click in the KDERIV and/or KPROP boxes and make the required changes. The ideal response is shown in section 6.6.4.