Baldor MN1928 Input / Output, Location, Name, Description, NextMove ES, 96-pin, connector

Models: MN1928

1 110
Download 110 pages 20.08 Kb
Page 53
Image 53
Manual background

5.3.7 Digital outputs 8-11

 

Location

X5

 

 

5

 

Mating connector: Weidmüller Omnimate BL 3.5/5

 

 

 

 

Pin

Name

Description

NextMove ES

 

 

 

 

 

96-pin

 

 

 

 

connector

 

 

 

 

 

1

5

DGND

Digital ground

a3

 

 

 

 

 

4

DOUT11

Digital output DOUT11

c22

 

 

 

 

 

 

3

DOUT10

Digital output DOUT10

c16

 

 

 

 

 

 

2

DOUT9

Digital output DOUT9

b13

 

 

 

 

 

 

1

DOUT8

Digital output DOUT8

a13

 

 

 

 

 

Manual background CAUTION: Digital outputs DOUT8 - DOUT11 on the backplane are not buffered by the opto-isolator card; they are connected directly to the NextMove ES outputs.

When an output is activated, it is grounded through the ULN2003, which can sink up to 50mA per output (all outputs on, 100% duty cycle). If an output is used to drive a relay, a suitably rated diode must be fitted across the relay coil, observing the correct polarity. This is to protect the output from the back-EMF generated by the relay coil when it is de-energized.

NextMove ES

 

 

 

 

96

 

ULN2003

pin

 

connector

MintMT

74AHCT244

 

OUTX.8

 

GND

 

 

Backplane

1

5

’X5’

DOUT8

DGND

User supply 24V

Output Load (Relay with flyback diode shown)

User supply

Manual background GND

Figure 24 - Digital output circuit (DOUT8-11) - DOUT8 shown

MN1928

Input / Output 5-21

Page 53
Image 53
Baldor MN1928 installation manual Input / Output, Location, Name, Description, NextMove ES, 96-pin, connector