B-12 Parameter Table MN792
Table B-2 Parameters Listed by Name Continued
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
84 RO Drive Enable DIAGNOSTICS Diagnostics 0 : Disabled 1 : Enabled Disabled cc Output
376 RO Drive Running DIAGNOSTICS Unallocated 0 : False 1 : True False kg Output
82 RO Drive Start DIAGNOSTICS Diagnostics 0 : Off 1 : On Off ca Output
177 RW EMF GAIN SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0.00 to 100.00 0.30 ex
176 RW EMF LAG SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0.00 to 200.00 40.00 ew
175 RW EMF LEAD SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0.10 to 50.00 2.00 ev
408 RW Enable SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0 : Disabled 1 : Enabled Enabled lc
497 RO Enable SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On On nt Output
206 RO Encoder DIAGNOSTICS Diagnostics xxxxx RPM 0 RPM fq Output
92 RW Encoder Alarm SETUP PARAMETERS::INHIBIT ALARMS Alarms 0 : Enabled 1 : Inhibited Enabled ck
24 RW Encoder Lines CONFIGURE DRIVE Calibration 10 to 5000 1024 ao 2
22 RW Encoder RPM CONFIGURE DRIVE Calibration 0 to 6000 RPM 1750 RPM am
49 RW ENCODER SIGN CONFIGURE DRIVE Speed Loop 0 : Negative 1 : Positive Positive bd 2
120 RW Enter Password PASSWORD 0x0000 to 0xFFFF 0x0000 dc 1
332 RW Error Report SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::BISYNCH SUPPORT
System Port P3 0x0000 to 0xFFFF 0x00C0 j8 1
288 RW External Reset SETUP PARAMETERS::RAMPS Ramps 0 : Disabled 1 : Enabled Disabled i0
307 RW External Reset SETUP PARAMETERS::RAISE/LOWER Raise/Lower 0 : False 1 : True FALSE ij
136 RW Feed Forward SETUP PARAMETERS::CURRENT LOOP Current Loop 0.10 to 50.00 2.00 ds 4
524 RW Field Current CONFIGURE DRIVE Calibration 0.2 to 4.0 AMPS 0.2 Amps ok 3
183 RO Field Demand DIAGNOSTICS Field Control xxx.xx % 0.00% f3 Output
170 RW Field Enable SETUP PARAMETERS::FIELD CONTROL Field Control 0 : Disabled 1 : Enabled Enabled eq 2
169 RO Field Enabled DIAGNOSTICS Field Control 0 : Disabled 1 : Enabled Disabled ep Output
19 RW Field Fail SETUP PARAMETERS::INHIBIT ALARMS Alarms 0 : Enabled 1 : Inhibited Enabled aj
182 RW Field I CAL. SETUP PARAMETERS::CALIBRATION Calibration 0.9800 to 1.1000 1.0000 f2
300 RO FIELD I FBK. DIAGNOSTICS Diagnostics xxx.xx % 0.00% ic Output
539 RO Field I FBK.AMPS DIAGNOSTICS Current Loop xxxx.x AMPS 0.0 Amps oz Output, 1, 3
617 RW Field I Thresh SETUP PARAMETERS::FIELD CONTROL Field Control 0.00 to 100.00 % 80.00%
403 RW FILTER T.C. SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0.000 to 10.000 Secs 0.100 Secs l7
186 RW FLD. QUENCH
MODE
SETUP PARAMETERS::FIELD CONTROL Field Control 0 : Quench 1 : Standby Quench f6
174 RW FLD. WEAK ENABLE SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0 : Disabled 1 : Enabled Disabled eu 2
209 RW FLD.CTRL MODE CONFIGURE DRIVE Field Control 0 : Voltage Control
1 : Current Control
Voltage Control ft 2
184 RO FLD.FIRING ANGLE DIAGNOSTICS Field Control xxx.xx DEG 0.00 Deg f4 Output
185 RW FLD.QUENCH
DELAY
SETUP PARAMETERS::FIELD CONTROL Field Control 0.0 to 600.0 Secs 0.0 Secs f5
210 RW FLD.VOLTS RATIO CONFIGURE DRIVE Field Control 0.00 to 100.00 % (h) 67.0% fu
516 RW Forward SETUP PARAMETERS::OP STATION::START
UP VALUES
Op Station 0 : False 1 : True TRUE oc
37 RW FULL MENUS MENUS Menus 0 : Disabled 1 : Enabled Enabled b1
329 RW GROUP ID (GID) SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::BISYNCH SUPPORT
System Port P3 0x0000 to 0x0007 0x0000 j5
122 RO Health LED DIAGNOSTICS Alarms 0 : False 1 : True True de Output
116 RO Health Store ALARM STATUS Alarms 0x0000 to 0xFFFF 0x0000 d8 Output
115 RO Health Word ALARM STATUS Alarms 0x0000 to 0xFFFF 0x0200 d7 Output
119 RW I DMD. ISOLATE SETUP PARAMETERS::CURRENT LOOP Current Loop 0 : Disabled 1 : Enabled Disabled db
274 RW I GAIN IN RAMP SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED
Advanced 0.0000 to 2.0000 1.0000 hm
66 RO IaDmd UNFILTERED DIAGNOSTICS Current Loop xxx.xx % (h) 0.0% bu Output
65 RO IaFbk UNFILTERED DIAGNOSTICS Current Loop xxx.xx % (h) 0.0% bt Output
93 RW IMAX BRK1(SPD1) SETUP PARAMETERS::CURRENT PROFILE Current Profile 0.00 to 200.00 % (h) 200.00% cl 2
33 RW IMAX BRK2(SPD2) SETUP PARAMETERS::CURRENT PROFILE Current Profile 0.00 to 200.00 % (h) 200.00% ax 2
256 RW Increase Rate SETUP PARAMETERS::RAISE/LOWER Raise/Lower 0.1 to 600.0 Secs 10.0 Secs h4
309 RW Input 0 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 -200.00 to 200.00 % 0.00% il
100 RW Input 1 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 -200.00 to 200.00 % 0.00% cs
410 RW Input 1 SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -300.00 to 300.00 % 0.00% le