Parameter Table B-13MN792
Table B-2 Parameters Listed by Name Continued
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
411 RW Input 2 SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -300.00 to 300.00 % 0.00% lf
423 RW Input 2 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 -200.00 to 200.00 % 0.00% lr
202 RW INT. DEFEAT SETUP PARAMETERS::SPEED LOOP Speed Loop 0 : Off 1 : On Off fm
409 RW INT. DEFEAT SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0 : Off 1 : On Off ld
17 RW INT. GAIN SETUP PARAMETERS::CURRENT LOOP Current Loop 0.00 to 200.00 3.50 ah
172 RW INT. GAIN SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS
Field Control 0.00 to 100.00 1.28 es
402 RW INT.TIME.CONST SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0.01 to 100.00 Secs 5.00 Secs l6
203 RO Inverse Time O/P DIAGNOSTICS Inverse Time xxx.xx % 200.0% fn Output, 2, 4
620 RW Invert SETUP PARAMETERS::RAMPS Ramps 0 : False 1 : True False
359 RW Inverted SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 1 (B5)
Digout 1 (B5) 0 : False 1 : True FALSE jz
360 RW Inverted SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 2 (B6)
Digout 2 (B6) 0 : False 1 : True FALSE k0
361 RW Inverted SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 3 (B7)
Digout 3 (B7) 0 : False 1 : True FALSE k1
21 RW IR Compensation SETUP PARAMETERS::CALIBRATION Calibration 0.00 to 100.00 % 0.00% al
513 RW Jog Setpoint SETUP PARAMETERS::OP STATION::SET UP Op Station 0.00 to 100.00 % 5.00% o9 1
520 RW Jog Setpoint SETUP PARAMETERS::OP STATION::START
UP VALUES
Op Station 0.00 to 100.00 % 5.00% og
218 RW Jog Speed 1 SETUP PARAMETERS::JOG/SLACK Jog/Slack -100.00 to 100.00 % 20.00 % g2
219 RW Jog Speed 2 SETUP PARAMETERS::JOG/SLACK Jog/Slack -100.00 to 100.00 % -5.00 % g3
496 RO Jog/Slack SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On Off ns Output
528 RO Last Alarm ALARM STATUS Alarms 0x0000 : No Active Alarms
0x0001 : Over Speed
0x0002 : Missing Pulse
0x0004 : Field Over I
0x0008 : Heatsink Trip
0x0010 : Thermistor
0x0020 : Over Volts (VA)
0x0040 : SPD Feed back
0x0080 : Encoder Failed
0x0100 : Field Failed
0x0200 : 3 Phase Failed
0x0400 : Phase Lock
0x0800 : 5703 RCV Error
0x1000 : Stall Trip
0x2000 : Over I Trip
0xf005 : External Trip
0x8000 : Accts Failed
0xf001 : Autotune Error
0xf002 : Autotune Aborted
0xf200 : Config Enabled
0xf400 : No Keypad
0xf006 : Remote Trip
0xff05 : PCB Version
0xff06 : Product Code
No Active Alarms oo Output, 1
375 RW Limit SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 0.00 to 200.00 % 105.00% kf
517 RW Local SETUP PARAMETERS::OP STATION::START
UP VALUES
Op Station 0 : False 1 : True TRUE od
511 RW Local Key Enable SETUP PARAMETERS::OP STATION::SET UP Op Station 0 : False 1 : True TRUE o7
262 RW Lower Input SETUP PARAMETERS::RAISE/LOWER Raise/Lower 0 : False 1 : True FALSE ha
421 RW MAIN CURR. LIMIT SETUP PARAMETERS::CURRENT LOOP Current Loop 0.00 to 200.00 % 200.00% lp
527 RO Master Bridge SETUP PARAMETERS::CURRENT LOOP Current Loop 0 : Off 1 : On Off on Output, 1
357 RW Max Demand SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop 0.00 to 105.00 % 105.00% jx
231 RW Max Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 1 (A2)
Analog Input 1 -300.00 to 300.00 % 100.00% gf
234 RW Max Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 2 (A3)
Analog Input 2 -300.00 to 300.00 % 100.00% gi
237 RW Max Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 3 (A4)
Analog Input 3 -300.00 to 300.00 % 100.00% gl