Getting Started 3-5MN792
Table 3-1 Set Analog Input 1 for 4–20mA ContinuedAction Description Display Comments
Press M Access Configure I/O menu. CONFIGURE ENABLE
DISABLE
This is menu level 3. Before any
parameter values can be changed,
Configure Enable must be “Enabled”
(it is normally disabled”).
Press Change Configure Enable to Enabled. CONFIGURE ENABLE
ENABLED
Note that the LED’s on Keypad are
flashing until changed back to Disable.
Press E Access Configure I/O menu. CONFIGURE I/O
CONFIGURE ENABLE
Move back one menu level using the
E key.
Press Scroll to analog inputs menu. CONFIGURE I/O
ANALOG INPUTS
Press M Access analog inputs 1 menu. ANALOG INPUTS
ANIN1 (A2)
Press M Access Calibration menu. ANIN1 (A2)
CALIBRATION
This is menu level 4.
Press M View or change the Calibration value. CALIBRATION
1.0000
Use the and keys to change the
value. Press E when finished.
Press E ANIN1 (A2)
CALIBRATION
Press Scroll to next menu. ANIN1 (A2)
MAX VALUE
Press M View or change the MAX Value menu. MAX VALUE
100.00%
Use the and keys to change the
value. Press E when finished.
Press E ANIN1 (A2)
MAX VALUE
Press Scroll to next menu. ANIN1 (A2)
MIN VALUE
Press M View or change the MIN Value menu. MIN VALUE
–100.00%
Use the and keys to change the
value. Press E when finished.
Press E ANIN1 (A2)
MIN VALUE
Press Scroll to next menu. ANIN1 (A2)
DESTINATION TAG
Press M View or change the Destination tag
Value menu. DESTINATION TAG
100
Use the and keys to change the
value. Press E when finished.
Press E Press “E” several times to return to
the Configure Enable menu. ANIN1 (A2)
DESTINATION TAG
Press M Access Configure I/O menu. CONFIGURE I/O
CONFIGURE ENABLE
This is menu level 2.
Press M Access Configure I/O menu. CONFIGURE ENABLE
ENABLED
This is menu level 3. Before the
control can be used again, Configure
Enable must be “Disabled”.
Press Change Configure Enable to Disabled. CONFIGURE ENABLE
DISABLED
Note when is pressed, the keypad
will briefly display “calibrating”
followed by Disabled and all Keypad
LED’s stop blinking.
Press E CONFIGURE I/O
CONFIGURE ENABLE
Press the “E” key several times to move back through the menu items or press “PROG” to return to control operation.
Note: When changing a numeric value, pressing the “M” key will change the cursor position one digit to the left.