Parameter Table B-17MN792
Table B-2 Parameters Listed by Name Continued
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
269 RW SPD BRK1 (LOW) SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.00 to 100.00 % 1.00% hh
31 RW SPD BRK2 (HIGH) SETUP PARAMETERS::CURRENT PROFILE Current Profile 0.00 to 100.00 % (h) 100.00% av 2
270 RW SPD BRK2 (HIGH) SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.00 to 100.00 % 5.00% hi
547 RW SPD.FBK.FILTER SETUP PARAMETERS::SPEED LOOP Menus 0.000 to 1.000 0.000 p7
13 RW SPD.INT.TIME CONFIGURE DRIVE Speed Loop 0.001 to 30.000 Secs 0.500 Secs ad
272 RW SPD.INT.TIME SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.001 to 30.000 Secs 0.500 Secs hk
14 RW SPD.PROP.GAIN CONFIGURE DRIVE Speed Loop 0.00 to 200.00 10 ae
180 RW SPDFBK ALM LEVEL SETUP PARAMETERS::CALIBRATION Calibration 0.00 to 100.00 % (h) 50.00% f0
89 RO Speed Demand DIAGNOSTICS Stop Rates xxx.xx % 0.00% ch Output
297 RO Speed Error DIAGNOSTICS Diagnostics xxx.xx % -0.01% i9 Output
81 RW SPEED FBK ALARM SETUP PARAMETERS::INHIBIT ALARMS Alarms 0 : Enabled 1 : Inhibited Enabled c9
47 RW SPEED FBK SELECT CONFIGURE DRIVE Speed Loop 0 : Arm Volts Fbk
1 : Analog Tach
2 : Encoder
3 : Encoder/Analog
Arm Volts Fbk bb
2
472 RO SPEED FBK STATE ALARM STATUS Unallocated 0 : False 1 : True False n4 Output
207 RO Speed Feedback DIAGNOSTICS Diagnostics xxx.xx % 0.01% fr Output
549 RO Speed LOOP O/P DIAGNOSTICS Speed Loop -200 to 200 % 0.00% p9 Output, 2
63 RO Speed Setpoint DIAGNOSTICS Speed Loop xxx.xx % 0.00% br Output
294 RW SPT SUM 1 DEST SYSTEM::CONFIGURE I/O::BLOCK DIAGRAM Setpoint Sum 1
Output
0 to 549 289 i6 2, 3
86 RO SPT SUM OUTPUT DIAGNOSTICS Setpoint Sum 1 xxx.xx % 0.00% ce Output
263 RW Stall Threshold SETUP PARAMETERS::CALIBRATION Calibration 0.00 to 200.00 % 95.00% hb
28 RW Stall Trip SETUP PARAMETERS::INHIBIT ALARMS Alarms 0 : Enabled 1 : Inhibited Inhibited as
112 RO Stall Trip ALARM STATUS Alarms 0 : OK 1 : Failed OK d4 Output
224 RW Stall Trip Delay SETUP PARAMETERS::CALIBRATION Calibration 0.1 to 600.0 Secs 10.0 Secs g8
11 RW Standstill Logic SETUP PARAMETERS::STANDSTILL Standstill 0 : Disabled 1 : Enabled Disabled ab
68 RO Start (C3) DIAGNOSTICS Aux I/O 0 : Off 1 : On Off bw Output
217 RW Stop Limit SETUP PARAMETERS::STOP RATES Stop Rates 0.0 to 600.0 Secs 60.0 Secs g1
27 RW Stop Time SETUP PARAMETERS::STOP RATES Stop Rates 0.1 to 600.0 Secs 10.0 Secs ar
29 RW Stop Zero Speed SETUP PARAMETERS::STOP RATES Stop Rates 0.00 to 100.00 % 2.00% at
374 RO System Reset DIAGNOSTICS Unallocated 0 : False 1 : True True ke Output
308 RO Tach Input DIAGNOSTICS Diagnostics xxx.xx % (h) 0.0% ik Output
253 RW Take Up 1 SETUP PARAMETERS::JOG/SLACK Jog/Slack -100.00 to 100.00 % 5.00% h1
254 RW Take Up 2 SETUP PARAMETERS::JOG/SLACK Jog/Slack -100.00 to 100.00 % -5.00% h2
506 RO TEC Option Fault SERIAL LINKS::TEC OPTION Tec Option 0 : None
1 : Parameter
2 : Type Mismatch
3 : Self Test
4 : Hardware
5 : Missing
None o2 Output
501 RW TEC Option IN 1 SERIAL LINKS::TEC OPTION Tec Option -32768 to 32767 0nx
502 RW TEC Option IN 2 SERIAL LINKS::TEC OPTION Tec Option -32768 to 32767 0ny
503 RW TEC Option IN 3 SERIAL LINKS::TEC OPTION Tec Option -32768 to 32767 0nz
504 RW TEC Option IN 4 SERIAL LINKS::TEC OPTION Tec Option -32768 to 32767 0o0
505 RW TEC Option IN 5 SERIAL LINKS::TEC OPTION Tec Option -32768 to 32767 0o1
508 RO TEC Option OUT 1 SERIAL LINKS::TEC OPTION Tec Option xxxxx 0o4 Output, 1
509 RO TEC Option OUT 2 SERIAL LINKS::TEC OPTION Tec Option xxxxx 0o5 Output, 1
500 RW TEC Option Type SERIAL LINKS::TEC OPTION Tec Option 0 : None
1 : Rs485
2 : Profibus Dp
3 : Link
4 : Device Net
5 : Can Open
6 : Lonworks
7 : Type 7
None nw
507 RO TEC Option VER SERIAL LINKS::TEC OPTION Tec Option 0x0000 to 0xFFFF 0x0000 o3 Output, 1