Programming 6-35MN792
Ramps This function block provides the facility to control the rate at which the control will respond to a changing
setpoint.
1 SETUP PARAMETERS
2 RAMPS
Ramp ACCEL Time
Ramp DECEL Time
Constant ACCEL
Ramp Hold
% S-Ramp
Ramping Thresh
Auto Reset
External Reset
Reset Value
MIN Speed
[5] Ramp Input 0.00%
[126] Min Speed 0.00%
Tag Parameter
[286] Ramping Threshold 0.50%
RAMPS
Factory Setting
t
[288] External Reset Disabled
[287] Auto Reset Enabled
[2] Ramp Accel Time 10.00 Sec
[3] Ramp Decel Time 10.00 Sec
Ramp Output
To Speed Loop
[266] % S Ramp 2.50%
S/Linear
Ramp
[113] Ramping
-
+
[293]
[118] Ramp Hold Off
Drive Enable
[293] Ramp O/p Dest 291
Diagnostic
connection
[85]
[422] Reset Value 0.00%
[496] Jog/Slack Off
[253] Take Up 1 +5.00%
[254] Take Up 2 -5.00%
Tag Parameter Factory Setting
[225] Crawl Speed 10.00%
[355] Ramp Rate 1.0 Seconds
Jog / Slack
[218] Jog Speed 1 +5.00%
[219] Jog Speed 2 -5.00%
[212] Operating Mode Operating Mode
Stop
Stop
Run
Take Up Slack 1
Take Up Slack 2
Jog 1
Jog 2
Crawl
Mode
False
True
False
False
True
False
True
True
Jog
Off
Off
Off
On
Off
On
On
On
Run
Off
Off
On
On
On
Off
Off
On
O/P
S/P
S/P
S/P
S/P + Take Up 1
S/P + Take Up 2
Jog Speed 1
Jog Speed 2
Crawl Speed
Jog
Ramp Rate
Jog Start
O/PS/P
From
AUX I/O
[102][C6]
DIG IN 1
S/P
O/P
[620] Ramp Invert False
[C5]
DIG IN R
[228] Mode False
[105][C7]
DIG IN 2
Stop
Parameter Descriptions
Ramp Output (Read in Diagnostics Parameters)
Refer to the diagnostics function block description. Range: xxx.xx %
Ramping (Read in Diagnostics Parameters)
Refer to the diagnostics function block description. Range: 0 : False
1 : True
Ramp Accel Time
Acceleration time (100% change) Range: 0.1 to 600.0 Seconds
Ramp Decel Time
Deceleration time (100% change) Range: 0.1 to 600.0 Seconds
Constant Accel
Reserved parameter. Range: 0 : Disabled
1 : Enabled
Ramp Hold
While ON, the ramp output is held at its last value. This is overridden by Ramp Reset. Range: 0 : Off
1 : On
Ramp Input
Ramp input tag. Range: –105.00 to 105.00 %
% S–Ramp
Percentage of ramp with S–shaped rate of change. A value of zero is equivalent to a linear ramp.
Changing this value affects the ramp times.
Range: 0.00 to 100.00 %
Ramping Thresh.
Ramping flag threshold level. The threshold is used to detect whether the ramp is active. Range: 0.00 to 100.00 %
Auto Reset
If true, then the ramp is reset whenever System Reset is true, that is each time the speed/current
loop is unquenched. (System Reset [374] is an internal flag that is set true for one cycle after the
speed/current loop is enabled, i.e. every time the drive is started).
Range: 0 : Disabled
1 : Enabled
External Reset
If true, then the ramp is held in reset. External reset does not depend on auto reset for its operation. Range: 0 : Disabled
1 : Enabled