Carrier 33CSPREMLK specifications Submaster Center

Models: 33CSPREMLK

1 44
Download 44 pages 4.58 Kb
Page 35
Image 35
–20.0 to 20.0 –5.5
Range: Default Value:
SUBMASTER GAIN LIMIT — The Submaster Gain Limit is used to define the submaster gain limit that is multiplied by the Submaster Error and added to the Submaster Center Value to produce the output value that will be sent to the device. The sign of the submaster gain limit determines the direction in which the output will be driven in response to a given error.
The gain is expressed in percent change in output per degree of error.
Submaster Gain
Limit Reference:
Range: Default Value:
Integral Gain: Derivative Gain: Starting Value:
Range: Default Value: Range: Default Value: Range: Default Value: Units:
–100.0 to 100.0 –4.0
–5.0 to 5.0 –2.0–20.0 to 20.0 –3.0
Degrees F
(Degrees C)
48.0 to 120.0
70.0
ECONOMIZER PID — The proportional gain determines the response of the PID temperature control loop; a larger gain increases the amount of damper movement while a smaller gain requires a larger error to achieve the same results.
The integral gain affects the response of a PID calculation; an increase in gain will compensate more quickly for propor- tional control droop. Too large of an integral gain will cause excessive damper positioning and instability. Enter the desired integral gain for the damper control algorithm.
The economizer derivative gain has been tested for ideal operation in sensor mode and should be left at the default value.
NOTE: In thermostat mode, the modulation may appear to regularly change. However, it will precisely control leaving-air temperature.
The economizer Starting Value is used to establish the start- ing value for the damper PID calculation. The value entered is determined by the mass of the zone. Typically a value of 10%, the default, will be adequate for most applications. For higher mass areas, such as a stone lobby, the value may be increased to 20 to 25%.
The Economizer PID includes the following set points: Proportional Gain, Integral Gain, Derivative Gain, and Starting Value.
Proportional Gain:
Starting Value:
Derivative Gain:
Integral Gain:
The integral gain affects the PID calculation; an increase will make the IAQ submaster reference change greater as the error in indoor air quality increases. The integral gain should be selected to eliminate proportional droop without overshoot. Enter the desired integral gain for the Indoor Air Quality con- trol algorithm.
The Derivative Gain is typically not required for Indoor Air Quality operation and should be left at the default value.
The Starting Value is used to establish the starting value for the IAQ PID calculation.
The IAQ PID includes the following set points: Proportion- al Gain, Integral Gain, Derivative Gain, and Starting Value.
Proportional Gain:Range: –100.0 to 40.0 Default Value: 1.0
Range: –5.0 to 5.0
Default Value: 0.5
Range: –20.0 to 20.0
Default Value: 0.0
Units: Percent
Range: 0.0 to 100.0
Default Value: 0.0

SUBMASTER CENTER VALUE — The Submaster Center Value is used to define the submaster loop center value which defines the starting point of the loop. This value typically repre- sents the midpoint of the range of the device being controlled.

Submaster Center

 

 

Value Reference:

Units:

Percent

 

Range:

0 to 100

 

Default Value:

60

DAMPER MOVEMENT BAND — The Damper Movement Band is used to define what the minimum desired range of change in economizer damper position that is required before the controller will attempt to open/close the economizer.

Damper Movement

Reference: Units: Percent

Range: 0 to 5

Default Value: 0

OAT TEMP BAND — The OAT Temp Band is used to slow the response of the economizer damper based on the value of OAT. In other words, the colder OAT gets the slower the rate of change in the economizer.

OAT Temp

Reference: Range: 0 to 40 Delta Degrees F (Delta Degrees C)

Default Value: 25.0

MINIMUM DAMPER POSITION — The minimum damper position (MDP) specifies user configured occupied minimum economizer damper position. The control selects the greatest value between MDP and IAQ calculated Minimum Position. The resulting value is the Final Minimum Damper Position IQMP for Occupied mode.

Economizer Damper is limited to IQMP in Occupied mode, or whenever Supply Fan is ON in units with Thermostat control.

Minimum Damper

Position: Units: Percent

Range: 0 to 100

Default Value: 20.0

LOW TEMP MINIMUM DAMPER POSITION OVER- RIDE — The Low Temperature Minimum Damper Position (MDP) specifies the value for purge minimum damper position for low outdoor air temperature conditions.

The IAQ Pre-Occupancy Purge Algorithm shall use this value for the minimum damper position whenever Outdoor Air Temperature is below Unoccupied OAT Lockout Temperature.

The Low Temperature MDP must be lower than the config- ured Minimum Damper Position.

Low Temperature

 

 

MDP Override:

Units:

Percent

 

Range:

0 to 100

 

Default Value:

100

DX COOLING LOCKOUT — The DX (Direct Expansion) Cooling Lockout function Enables/Disables Low Ambient DX Cooling Lockout option.

For Version 1.2 — When DX Cooling Lockout is enabled, Cooling control will compare OAT against the DX Cooling Lockout Temperature. Whenever OAT <= the DX Cooling Lockout Temperature and current DX stages are 0, the control will set Cooling Submaster Reference (CCSR) to 150 F. That will prevent the unit from staging up.

If the OAT sensor is not installed (OAT point reads –40 F and “Sensor Failure”), the cooling stages ARE locked out if DXCTLO is On.

35

Page 35
Image 35
Carrier 33CSPREMLK specifications Submaster Center