To access the
SETP
OATL >NTLO
UHDB
To view an expansion of the
and ESCAPE keys simultaneously and the Navigator will
display:
>NTLO
UNOCC. OAT LOCKOUT TEMP
The Navigator will remain in the expanded display mode
until the ESCAPE key is pressed. Use the arrow keys to view
expansions for any of the other
Password Protection — If an area is entered that is password protected or an item is selected for change that is password protected, the Navigator will display:
Enter Password
1111 (default password)
The first digit of the password will be flashing. Hold either of the arrow keys down to change the value of the first digit (if
necessary) and press ENTER to accept. Repeat the process for
the remaining three digits.
The message “Invalid Password” is displayed if the pass- word is not correct. The password can not be disabled from the Navigator, nor can it be changed.
Forcing Values and Configuring Items — Cer- tain items are allowed to be forced and other items are user- configurable. Both of these changes can be made using the Navigator.
CONFIGURATION
The following sections describe the computer configuration screens which are used to configure the PremierLink™ con- troller. The screens shown may be displayed differently when using different Carrier software.
Points Display Screen — The Points Display screen is used to monitor and change the PremierLink controller set points. See Table 7.
SPACE TEMPERATURE — This point displays the space temperature from the 10K thermistor (Type III) located in the space.
Space |
|
|
Temperature: | Display Units: | Degrees F (Degrees C) |
| Default Value: | |
| Display Range: | |
| Network Access: | Read/Write |
SUPPLY AIR TEMPERATURE — The Supply Air Temper- ature point displays the temperature of the air leaving the unit, downstream of any cool or heat sources. Temperature is mea- sured by a 10K thermistor (Type III). This sensor is required for proper function of the heating, cooling, and the economizer.
Supply Air |
|
|
Temperature: | Display Units: | Degrees F (Degrees C) |
| Default Value: | 0.0 |
| Display Range: | |
| Network Access: | Read/Write |
OUTDOOR AIR TEMPERATURE — Temperature of the air leaving the unit downstream of any cool or heat sources, measured by a 10K thermistor (Type III). This sensor is required for proper function of the heating, cooling, and the economizer.
Outdoor Air |
|
|
Temperature: | Display Units: | Degrees F (Degrees C) |
| Default Value: | 0.0 |
| Display Range: | |
| Network Access: | Read/Write |
CONTROL SET POINT — This point displays the current controlling set point when a heat or cool mode is active. If there is not an active heat or cool set point, the set point of the last mode is displayed. Upon reset or
Control Set Point: Display Units: | Degrees F (Degrees C) |
Default Value: | Unoccupied Cool |
| Setpoint |
Display Range: | 35 to 110 |
Network Access: | Read Only |
COOLING PERCENT TOTAL CAPACITY — The Cooling Percent Total Capacity point is used to display the current Cooling Capacity. When cooling is enabled, the percent of cooling being delivered is determined by the following formula for the number of compressor stages confirmed:
% Output Capacity = (# of active stages/Total stages) * 100.
Cooling Percent |
|
Total Capacity: Display Units: | % output capacity |
Default Value: | 0 |
Display Range: | 0 to 100 |
Network Access: | Read Only |
HEATING PERCENT TOTAL CAPACITY — The Heating Percent Total Capacity point is used to display the current Heating Capacity.
When heat is enabled, the percent of heat being delivered is determined by the following formula for electric heat:
% Output Capacity = (# of active stages/Total stages) * 100
Heating Percent |
|
Total Capacity: Display Units: | % output capacity |
Default Value: | 0 |
Display Range: | 0 to 100 |
Network Access: | Read Only |
ECONOMIZER ACTIVE — The Economizer Active point displays the status of the economizer for free cooling. When the outdoor conditions match the desired indoor conditions, the economizer will be enabled for outdoor air assisted cooling.
Economizer
Active: Display Units: Discrete ASCII Default Value: No
Display Range: No/Yes
Network Access: Read Only
SUPPLY FAN RELAY — This point displays the command- ed state of the Supply Fan Relay.
Supply Fan
Relay: Display Units: Discrete ASCII Default Value: Off
Display Range: Off/On
Network Access: Read/Write
28