Carrier 48/50HJ004-014 specifications

Models: 48/50HJ004-014

1 44
Download 44 pages 2.92 Kb
Page 13
Image 13
control box. See Fig. 10. The raceway provides the UL required clearance between high- and low-voltage wiring.

NOTE: For wire runs up 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

Pass the control wires through the hole provided in the cor- ner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the

control box. See Fig. 10. The raceway provides the UL required clearance between high- and low-voltage wiring.

NOTE: A humidistat and a temperature sensor can be used in place of a thermidistat for PremierLink™ units.

HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for the first stage and .14 amp for second- stage heating, when available.

Table 1A — Electrical Data (COBRA™ Energy Recovery 48HJ004-007 Units with 62AQ060)

 

NOMINAL

IFM

CONV

62AQ

POWER SUPPLY

DISCONNECT SIZE*

UNIT

V-PH-Hz

TYPE

OUTLET

FLA

MCA

FUSE OR

FLA

LRA

 

HACR BKR

 

 

 

 

 

 

 

 

 

208/230-1-60

STD

NO

9.2

34.8/34.8

40/40

35/35

135/135

 

STD

YES

9.2

40.8/40.8

45/45

41/41

140/140

 

 

 

 

STD

NO

9.2

27.7/27.7

35/35

29/29

124/124

 

208/230-3-60

STD

YES

9.2

33.7/33.7

40/35

34/34

129/129

 

HIGH STATIC

NO

9.2

28.6/28.6

35/35

30/30

154/154

48HJ004

 

 

HIGH STATIC

YES

9.2

34.6/34.6

40/40

35/35

158/158

 

 

 

 

STD

NO

9.2

13.6

20

14

63

 

460-3-60

STD

YES

9.2

16.3

20

20

67

 

 

HIGH STATIC

NO

9.2

14.0

20

15

77

 

 

HIGH STATIC

YES

9.2

16.7

20

20

82

 

208/230-1-60

STD

NO

9.2

44.4/44.4

60/60

44/44

173/173

 

STD

YES

9.2

50.4/50.4

60/60

50/50

178/178

 

 

 

 

STD

NO

9.2

31.7/31.7

40/40

33/33

140/140

 

208/230-3-60

STD

YES

9.2

37.7/37.7

40/40

38/38

145/145

48HJ005

 

HIGH STATIC

NO

9.2

32.6/32.6

40/40

34/34

170/170

 

HIGH STATIC

YES

9.2

38.6/38.6

45/45

39/39

174/174

 

 

 

 

STD

NO

9.2

15.2

20

16

70

 

460-3-60

STD

YES

9.2

17.9

20

21

75

 

HIGH STATIC

NO

9.2

15.6

20

16

84

 

 

 

 

HIGH STATIC

YES

9.2

18.3

20

22

89

 

208/230-1-60

STD

NO

9.2

55.5/55.5

70/70

56/56

250/250

 

STD

YES

9.2

61.5/61.5

70/70

61/61

255/255

 

 

 

 

STD

NO

9.2

38.1/38.1

45/45

39/39

202/202

 

208/230-3-60

STD

YES

9.2

44.1/44.1

50/50

44/44

207/207

 

HIGH STATIC

NO

9.2

39.8/39.8

45/45

41/41

221/221

48HJ006

 

 

HIGH STATIC

YES

9.2

45.8/45.8

50/50

46/46

226/226

 

 

 

 

STD

NO

9.2

19.3

25

20

101

 

460-3-60

STD

YES

9.2

22.0

25

25

106

 

HIGH STATIC

NO

9.2

20.1

25

20

110

 

 

 

 

HIGH STATIC

YES

9.2

22.8

25

26

115

 

208/230-3-60

STD

NO

9.2

42.0/42.0

50/50

42/42

234/234

 

STD

YES

9.2

48.0/48.0

60/60

48/48

239/239

 

 

 

208/230-3-60

HIGH STATIC

NO

9.2

43.7/43.7

50/50

44/44

253/253

 

HIGH STATIC

YES

9.2

49.7/49.7

60/60

50/50

258/258

48HJ007

 

 

STD

NO

9.2

19.8

25

20

114

 

 

 

460-3-60

STD

YES

9.2

22.5

25

26

118

 

HIGH STATIC

NO

9.2

20.6

25

21

123

 

 

 

 

HIGH STATIC

YES

9.2

23.3

30

26

128

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

UL

Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of volt- age imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, con- tact your local electric utility company immediately.

13

Page 13
Image 13
Carrier 48/50HJ004-014 specifications