Carrier 48/50HJ004-014 specifications 20.9

Models: 48/50HJ004-014

1 44
Download 44 pages 2.92 Kb
Page 19
Image 19
Manual background

Table 1D — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ100) (cont)

 

 

 

 

 

HEATER

HEAT

 

POWER SUPPLY

 

 

SINGLE

DISCONNECT SIZE*

UNIT

NOMINAL

IFM

CONV

62AQ

CRHEATER

 

 

 

FUSE OR

 

 

POINT BOX

 

 

 

V-PH-Hz

TYPE

OUTLET

FLA

FLA

MCA

MOCP

CRSINGLE

FLA

LRA

 

---A00

HACR BKR

 

 

 

 

 

 

 

 

 

 

---A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE

20.9

25

 

25

 

88

 

 

STD

YES

15.1

006

7.2

22.2

30

 

25

 

88

 

 

008

13.8

30.5

35

 

025

25

 

88

 

 

 

 

 

009

16.8

34.2

40

 

025

35

 

88

 

 

 

 

 

008+008

27.7

47.7

50

 

025

48

 

96

 

 

 

 

 

NONE

18.6

25

 

19

 

97

50HJ005

460-3-60

HIGH STATIC

NO

15.1

006

7.2

20.5

25

 

19

 

98

(cont)

008

13.8

28.8

35

 

025

19

 

98

 

 

 

 

 

009

16.8

32.5

35

 

025

31

 

98

 

 

 

 

 

008+008

27.7

46.0

50

 

025

43

 

108

 

 

 

 

 

NONE

21.3

25

 

25

 

102

 

 

HIGH STATIC

YES

15.1

006

7.2

22.6

30

 

25

 

103

 

 

008

13.8

30.9

35

 

025

25

 

103

 

 

 

 

 

009

16.8

34.6

40

 

025

36

 

103

 

 

 

 

 

008+008

27.7

48.1

50

 

025

48

 

110

 

 

 

 

 

NONE

—/—

61.4/ 61.4

70/70

 

62/ 62

276/276

 

 

 

 

 

002

23.5/27.1

61.4/

61.4

70/

70

004

62/

62

276/276

 

 

STD

NO

15.1

003

31.4/36.3

65.8/

71.8

70/

80

004

64/

69

276/276

 

 

002+002

46.9/54.2

85.2/

94.2

90/100

005

81/

90

276/276

 

 

 

 

 

 

 

 

 

 

003+003

62.8/72.5

105.1/117.2

110/125

005

100/111

276/276

 

208/230-1-60

 

 

 

004+004

75.8/87.5

121.3/135.9

125/150

005

115/128

276/276

 

 

 

 

NONE

—/—

67.4/ 67.4

80/80

 

68/ 68

281/281

 

 

 

 

 

 

 

 

 

 

 

002

23.5/27.1

67.4/

67.4

80/

80

004

68/

68

281/281

 

 

STD

YES

15.1

003

31.4/36.3

70.6/

76.0

80/

80

005

69/

74

281/281

 

 

002+002

46.9/54.2

90.0/

98.4

90/100

005

87/

95

281/281

 

 

 

 

 

 

 

 

 

 

003+003

62.8/72.5

109.9/121.4

110/125

005

105/116

281/281

 

 

 

 

 

004+004

75.8/87.5

126.1/140.1

150/150

005

120/133

281/281

 

 

 

 

 

NONE

—/—

44.0/ 44.0

50/50

 

46/ 46

228/228

 

 

 

 

 

002

13.6/15.6

44.0/

44.0

50/50

 

46/

46

228/228

 

 

STD

NO

15.1

004

21.9/25.3

50.9/

55.1

60/60

 

49/

53

228/228

 

 

005

33.4/38.5

65.2/

71.6

70/

80

002

62/

68

228/228

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

78.2/

86.7

80/

90

003

74/

82

228/228

 

 

 

 

 

004+005

55.2/63.8

92.6/103.2

100/110

003

88/

97

228/228

 

 

 

 

 

NONE

—/—

50.0/ 50.0

60/60

 

51/ 51

233/233

 

 

 

 

 

002

13.6/15.6

50.0/

50.0

60/60

 

51/

51

233/233

50HJ006

 

STD

YES

15.1

004

21.9/25.3

55.7/ 59.3

70/ 70

002

55/ 58

233/233

 

 

 

 

 

005

33.4/38.5

70.0/

75.8

80/

80

003

68/

73

233/233

 

 

 

 

 

004+004

43.8/50.5

83.0/

90.9

90/100

003

80/

87

233/233

 

208/230-3-60

 

 

 

004+005

55.2/63.8

97.4/107.4

100/110

003

93/102

233/233

 

 

 

 

NONE

—/—

45.7/ 45.7

60/60

 

48/ 48

247/247

 

 

 

 

 

 

 

 

 

 

 

002

13.6/15.6

45.7/

45.7

60/60

 

48/

48

247/247

 

 

HIGH STATIC

NO

15.1

004

21.9/25.3

52.6/

56.8

60/

70

002

51/

55

247/247

 

 

005

33.4/38.5

66.9/

73.3

70/

80

002

64/

70

247/247

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

79.9/

88.4

80/

90

003

76/

84

247/247

 

 

 

 

 

004+005

55.2/63.8

94.3/104.9

100/110

003

90/

99

247/247

 

 

 

 

 

NONE

—/—

51.7/ 51.7

60/60

 

53/ 53

252/252

 

 

 

 

 

002

13.6/15.6

51.7/

51.7

60/60

 

53/

53

252/252

 

 

HIGH STATIC

YES

15.1

004

21.9/25.3

57.4/

61.0

70/

70

002

57/

60

252/252

 

 

005

33.4/38.5

71.7/

77.5

80/

80

003

70/

75

252/252

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

84.7/

92.6

90/100

003

82/

89

252/252

 

 

 

 

 

004+005

55.2/63.8

99.1/109.1

100/110

003

95/104

252/252

 

 

 

 

 

NONE

22.2

25

 

23

 

114

 

 

 

 

 

006

7.2

22.2

25

 

23

 

114

 

460-3-60

STD

NO

15.1

008

13.8

28.8

35

 

025

23

 

114

 

009

16.8

32.5

35

 

025

31

 

114

 

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

46.0

50

 

025

43

 

114

 

 

 

 

 

008+009

30.7

49.8

50

 

025

47

 

114

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

UL

Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir- cuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

=457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

7

457

= 1.53%

 

This amount of phase imbalance is satisfactory as it is below the maximum allow- able 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

19

Page 19
Image 19
Carrier 48/50HJ004-014 specifications 20.9