Table 1B — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ060) (cont)

 

 

 

 

 

HEATER

HEAT

 

POWER SUPPLY

 

 

SINGLE

DISCONNECT SIZE*

UNIT

NOMINAL

IFM

CONV

62AQ

CRHEATER

 

 

 

FUSE OR

 

 

POINT BOX

 

 

V-PH-Hz

TYPE

OUTLET

FLA

FLA

MCA

MOCP

CRSINGLE

FLA

LRA

 

---A00

HACR BKR

 

 

 

 

 

 

 

 

 

 

---A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE

20.1

25

 

20

110

 

 

 

 

 

006

7.2

20.1

25

 

20

111

 

 

HIGH STATIC

NO

9.2

008

13.8

26.2

30

 

20

111

 

 

009

16.8

29.9

30

 

29

111

 

 

 

 

 

 

50HJ006

 

 

 

 

008+008

27.7

43.5

45

 

025

41

111

460-3-60

 

 

 

008+009

30.7

47.2

50

 

025

44

111

(cont)

 

 

 

NONE

22.8

25

 

26

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

006

7.2

22.8

25

 

26

116

 

 

HIGH STATIC

YES

9.2

008

13.8

28.3

30

 

26

116

 

 

009

16.8

32.0

35

 

025

33

116

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

45.6

50

 

025

46

116

 

 

 

 

 

008+009

30.7

49.3

50

 

025

49

116

 

 

 

 

 

NONE

—/—

42.0/ 42.0

50/50

 

42/42

234/234

 

 

 

 

 

002

13.6/15.6

42.0/

42.0

50/50

 

42/42

234/234

 

 

STD

NO

9.2

004

21.9/25.3

44.1/

48.3

50/50

 

42/46

234/234

 

 

005

33.4/38.5

58.4/

64.9

60/

70

002

56/62

234/234

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

71.5/

79.9

80/

80

003

68/75

234/234

 

 

 

 

 

004+005

55.2/63.8

85.8/

96.4

90/100

003

81/91

234/234

 

 

 

 

 

NONE

—/—

48.0/ 48.0

60/60

 

48/48

239/239

 

 

 

 

 

002

13.6/15.6

48.0/

48.0

60/60

 

48/48

239/239

 

 

STD

YES

9.2

004

21.9/25.3

48.9/

52.5

60/60

 

48/51

239/239

 

 

005

33.4/38.5

63.2/

69.1

70/

70

003

61/66

239/239

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

76.3/

84.1

80/

90

003

73/80

239/239

 

208/230-3-60

 

 

 

004+005

55.2/63.8

90.6/100.6

100/110

003

86/95

239/239

 

 

 

 

NONE

—/—

43.7/ 43.7

50/50

 

44/44

253/253

 

 

 

 

 

 

 

 

 

 

 

002

13.6/15.6

43.7/

43.7

50/50

 

44/44

253/253

 

 

HIGH STATIC

NO

9.2

004

21.9/25.3

45.9/

50.1

50/60

 

44/48

253/253

 

 

005

33.4/38.5

60.3/

66.7

70/

70

003

58/63

253/253

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

73.3/

81.7

80/

90

003

70/77

253/253

 

 

 

 

 

004+005

55.2/63.8

87.6/

98.3

90/100

003

83/93

253/253

 

 

 

 

 

NONE

—/—

49.7/ 49.7

60/60

 

50/50

258/258

 

 

 

 

 

002

13.6/15.6

49.7/

49.7

60/60

 

50/50

258/258

 

 

HIGH STATIC

YES

9.2

004

21.9/25.3

50.7/

54.3

60/60

 

50/53

258/258

 

 

005

33.4/38.5

65.1/

70.9

70/

80

003

63/68

258/258

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

78.1/

85.9

80/

90

003

75/82

258/258

50HJ007

 

 

 

 

004+005

55.2/63.8

92.4/102.5

100/110

003

88/97

258/258

 

 

 

 

NONE

19.8

25

 

20

114

 

 

 

 

 

 

 

 

 

 

 

006

7.2

19.8

25

 

20

114

 

 

STD

NO

9.2

008

13.8

25.4

30

 

20

114

 

 

009

16.8

29.1

30

 

28

114

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

42.7

45

 

025

40

114

 

 

 

 

 

008+009

30.7

46.4

50

 

025

44

114

 

 

 

 

 

NONE

22.5

25

 

26

118

 

 

 

 

 

006

7.2

22.5

25

 

26

119

 

 

STD

YES

9.2

008

13.8

27.5

30

 

26

119

 

 

009

16.8

31.2

35

 

025

32

119

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

44.8

45

 

025

45

119

 

460-3-60

 

 

 

008+009

30.7

48.5

50

 

025

48

119

 

 

 

 

NONE

20.6

25

 

21

123

 

 

 

 

 

 

 

 

 

 

 

006

7.2

20.6

25

 

21

124

 

 

HIGH STATIC

NO

9.2

008

13.8

26.2

30

 

21

124

 

 

009

16.8

29.9

30

 

29

124

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

43.5

45

 

025

41

124

 

 

 

 

 

008+009

30.7

47.2

50

 

025

44

124

 

 

 

 

 

NONE

23.3

30

 

26

128

 

 

 

 

 

006

7.2

23.3

30

 

26

128

 

 

HIGH STATIC

YES

9.2

008

13.8

28.3

30

 

26

128

 

 

009

16.8

32.0

35

 

025

33

128

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

45.6

50

 

025

46

128

 

 

 

 

 

008+009

30.7

49.3

50

 

025

49

128

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

UL

Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir- cuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

=457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

7

457

= 1.53%

 

This amount of phase imbalance is satisfactory as it is below the maximum allow- able 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

16