Table 1E — Electrical Data (COBRA™ Energy Recovery 48HJ008-014 Units with 62AQ200)

 

NOMINAL

IFM

CONV

62AQ

POWER SUPPLY

DISCONNECT SIZE*

UNIT

 

FUSE OR

 

 

V-PH-HZ

TYPE

OUTLET

FLA

MCA

FLA

LRA

 

HACR BKR

 

 

 

 

 

 

 

 

 

 

STD

NO

21.9

60.1

70

66

366

 

208/230-3-60

STD

YES

21.9

66.1

70

71

371

 

HIGH STATIC

NO

21.9

63.2

70

69

391

 

 

48HJ008

 

HIGH STATIC

YES

21.9

69.2

80

75

395

 

STD

NO

10.2

29.4

35

32

184

 

 

 

460-3-60

STD

YES

10.2

32.1

35

34

186

 

HIGH STATIC

NO

10.2

30.8

35

34

197

 

 

 

 

HIGH STATIC

YES

10.2

33.5

35

36

199

 

 

STD

NO

21.9

62.1

70

68

400

 

208/230-3-60

STD

YES

21.9

68.1

70

73

405

 

HIGH STATIC

NO

21.9

65.2

70

71

425

 

 

48HJ009

 

HIGH STATIC

YES

21.9

65.2

70

71

425

 

STD

NO

10.2

31.7

35

34

206

 

 

 

460-3-60

STD

YES

10.2

34.4

40

37

208

 

HIGH STATIC

NO

10.2

33.1

35

36

219

 

 

 

 

HIGH STATIC

YES

10.2

35.8

40

38

221

 

 

STD

NO

21.9

74.9

80

81

465

 

208/230-3-60

STD

YES

21.9

80.9

90

87

469

 

HIGH STATIC

NO

21.9

79.3

90

86

488

 

 

48HJ012

 

HIGH STATIC

YES

21.9

85.3

90

92

493

 

STD

NO

10.2

35.1

40

38

234

 

 

 

460-3-60

STD

YES

10.2

37.8

40

40

236

 

HIGH STATIC

NO

10.2

37.7

40

41

245

 

 

 

 

HIGH STATIC

YES

10.2

40.4

45

43

247

 

208/230-3-60

STD

NO

21.9

82.5

90

89

550

 

STD

YES

21.9

88.5

100

95

555

48HJ014

 

460-3-60

STD

NO

10.2

39.3

45

43

270

 

 

STD

YES

10.2

42.0

45

45

272

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC — National Electrical Code

UL — Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:

1.In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.