Table 1G — Electrical Data (COBRA™ Energy Recovery 48HJ008-014 Units with 62AQ300)

 

NOMINAL

IFM

CONV

62AQ

POWER SUPPLY

DISCONNECT SIZE*

UNIT

 

FUSE OR

 

 

V-PH-Hz

TYPE

OUTLET

FLA

MCA

FLA

LRA

 

HACR BKR

 

 

 

 

 

 

 

 

 

 

STD

NO

29.8

68.0

80

75

420

 

208/230-3-60

STD

YES

29.8

74.0

80

80

425

 

HIGH STATIC

NO

29.8

71.1

80

78

445

 

 

48HJ008

 

HIGH STATIC

YES

29.8

77.1

80

84

449

 

STD

NO

15.8

35.0

40

38

211

 

 

 

460-3-60

STD

YES

15.8

37.7

40

41

213

 

HIGH STATIC

NO

15.8

36.4

40

40

224

 

 

 

 

HIGH STATIC

YES

15.8

39.1

45

43

226

 

 

STD

NO

29.8

70.0

80

77

454

 

208/230-3-60

STD

YES

29.8

76.0

80

82

459

 

HIGH STATIC

NO

29.8

73.1

80

80

479

 

 

48HJ009

 

HIGH STATIC

YES

29.8

79.1

80

86

483

 

STD

NO

15.8

37.3

40

41

233

 

 

 

460-3-60

STD

YES

15.8

40.0

45

43

235

 

HIGH STATIC

NO

15.8

38.7

45

42

246

 

 

 

 

HIGH STATIC

YES

15.8

41.4

45

45

248

 

 

STD

NO

29.8

82.8

90

90

519

 

208/230-3-60

STD

YES

29.8

88.8

100

96

523

 

HIGH STATIC

NO

29.8

87.2

100

95

542

 

 

48HJ012

 

HIGH STATIC

YES

29.8

93.2

100

101

547

 

STD

NO

15.8

40.7

45

44

261

 

 

 

460-3-60

STD

YES

15.8

43.4

45

47

263

 

HIGH STATIC

NO

15.8

43.3

50

47

272

 

 

 

 

HIGH STATIC

YES

15.8

46.0

50

50

274

 

208/230-3-60

STD

NO

29.8

90.4

100

98

604

 

STD

YES

29.8

96.4

100

104

609

48HJ014

 

460-3-60

STD

NO

15.8

44.9

50

49

297

 

 

STD

YES

15.8

47.6

50

51

299

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC — National Electrical Code

UL — Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:

1.In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

24

Page 24
Image 24
Carrier 48/50HJ004-014 specifications 68.0 420