Carrier 48/50HJ004-014 specifications 47.9

Models: 48/50HJ004-014

1 44
Download 44 pages 2.92 Kb
Page 20
Image 20
47.9/

Table 1D — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ100) (cont)

 

 

 

 

 

HEATER

HEAT

 

POWER SUPPLY

 

 

SINGLE

DISCONNECT SIZE*

UNIT

NOMINAL

IFM

CONV

62AQ

CRHEATER

 

 

 

FUSE OR

 

 

POINT BOX

 

 

 

V-PH-Hz

TYPE

OUTLET

FLA

FLA

MCA

MOCP

CRSINGLE

FLA

LRA

 

---A00

HACR BKR

 

 

 

 

 

 

 

 

 

 

---A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE

24.9

30

 

28

119

 

 

 

 

 

006

7.2

24.9

30

 

28

119

 

 

STD

YES

15.1

008

13.8

30.9

35

 

025

28

119

 

 

009

16.8

34.6

40

 

025

36

119

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

48.1

50

 

025

48

119

 

 

 

 

 

008+009

30.7

51.9

60

 

025

52

119

 

 

 

 

 

NONE

23.0

30

 

24

123

50HJ006

 

 

 

 

006

7.2

23.0

30

 

24

124

460-3-60

HIGH STATIC

NO

15.1

008

13.8

29.6

35

 

025

24

124

(cont)

009

16.8

33.3

35

 

025

32

124

 

 

 

 

 

 

 

 

 

 

008+008

27.7

46.8

50

 

025

44

124

 

 

 

 

 

008+009

30.7

50.6

60

 

025

48

124

 

 

 

 

 

NONE

25.7

30

 

29

128

 

 

 

 

 

006

7.2

25.7

30

 

29

129

 

 

HIGH STATIC

YES

15.1

008

13.8

31.7

35

 

025

29

129

 

 

009

16.8

35.4

40

 

025

37

129

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

48.9

50

 

025

49

129

 

 

 

 

 

008+009

30.7

52.7

60

 

025

53

129

 

 

 

 

 

NONE

—/—

47.9/ 47.9

60/60

 

49/ 49

260/260

 

 

 

 

 

002

13.6/15.6

47.9/

47.9

60/60

 

49/

49

260/260

 

 

STD

NO

15.1

004

21.9/25.3

50.9/

55.1

60/60

 

49/

53

260/260

 

 

005

33.4/38.5

65.2/

71.6

70/

80

002

62/

68

260/260

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

78.2/

86.7

80/

90

003

74/

82

260/260

 

 

 

 

 

004+005

55.2/63.8

92.6/103.2

100/110

003

88/

97

260/260

 

 

 

 

 

NONE

—/—

53.9/ 53.9

60/60

 

55/ 55

265/265

 

 

 

 

 

002

13.6/15.6

53.9/

53.9

60/60

 

55/

55

265/265

 

 

STD

YES

15.1

004

21.9/25.3

55.7/

59.3

70/

70

002

55/

58

265/265

 

 

005

33.4/38.5

70.0/

75.8

80/

80

003

68/

73

265/265

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

83.0/

90.9

90/100

003

80/

87

265/265

 

208/230-3-60

 

 

 

004+005

55.2/63.8

97.4/107.4

100/110

003

93/102

265/265

 

 

 

 

NONE

—/—

49.6/ 49.6

60/60

 

51/ 51

279/279

 

 

 

 

 

 

 

 

 

 

 

002

13.6/15.6

49.6/

49.6

60/60

 

51/

51

279/279

 

 

HIGH STATIC

NO

15.1

004

21.9/25.3

52.6/

56.8

60/

70

002

51/

55

279/279

 

 

005

33.4/38.5

66.9/

73.3

70/

80

002

64/

70

279/279

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

79.9/

88.4

80/

90

003

76/

84

279/279

 

 

 

 

 

004+005

55.2/63.8

94.3/104.9

100/110

003

90/

99

279/279

 

 

 

 

 

NONE

—/—

55.6/ 55.6

60/60

 

57/ 57

284/284

 

 

 

 

 

002

13.6/15.6

55.6/

55.6

60/60

 

57/

57

284/284

 

 

HIGH STATIC

YES

15.1

004

21.9/25.3

57.4/

61.0

70/

70

002

57/

60

284/284

 

 

005

33.4/38.5

71.7/

77.5

80/

80

003

70/

75

284/284

 

 

 

 

 

 

 

 

 

 

004+004

43.8/50.5

84.7/

92.6

90/100

003

82/

89

284/284

50HJ007

 

 

 

 

004+005

55.2/63.8

99.1/109.1

100/110

003

95/104

284/284

 

 

 

 

NONE

22.8

30

 

23

127

 

 

 

 

 

 

 

 

 

 

 

006

7.2

22.8

30

 

23

127

 

 

STD

NO

15.1

008

13.8

28.8

35

 

025

23

127

 

 

009

16.8

32.5

35

 

025

31

127

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

46.0

50

 

025

43

127

 

 

 

 

 

008+009

30.7

49.8

50

 

025

47

127

 

 

 

 

 

NONE

25.5

30

 

29

131

 

 

 

 

 

006

7.2

25.5

30

 

29

132

 

 

STD

YES

15.1

008

13.8

30.9

35

 

025

29

132

 

 

009

16.8

34.6

40

 

025

36

132

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

48.1

50

 

025

48

132

 

460-3-60

 

 

 

008+009

30.7

51.9

60

 

025

52

132

 

 

 

 

NONE

23.6

30

 

24

136

 

 

 

 

 

 

 

 

 

 

 

006

7.2

23.6

30

 

24

137

 

 

HIGH STATIC

NO

15.1

008

13.8

29.6

35

 

025

24

137

 

 

009

16.8

33.3

35

 

025

32

137

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

46.8

50

 

025

44

137

 

 

 

 

 

008+009

30.7

50.6

60

 

025

48

137

 

 

 

 

 

NONE

26.3

30

 

30

141

 

 

 

 

 

006

7.2

26.3

30

 

30

141

 

 

HIGH STATIC

YES

15.1

008

13.8

31.7

35

 

025

30

141

 

 

009

16.8

35.4

40

 

025

37

141

 

 

 

 

 

 

 

 

 

 

 

008+008

27.7

48.9

50

 

025

49

141

 

 

 

 

 

008+009

30.7

52.7

60

 

025

53

141

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

UL

Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir- cuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

=457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

7

457

= 1.53%

 

This amount of phase imbalance is satisfactory as it is below the maximum allow- able 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

20

Page 20
Image 20
Carrier 48/50HJ004-014 specifications 47.9