MAX WEIGHT

 

A

 

B

 

 

C

 

 

lb

kg

in.

mm

in

 

mm

in.

 

mm

48HJ004 w/62AQ060

890

404

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ004 w/62AQ100

905

411

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ005 w/62AQ060

900

409

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ005 w/62AQ100

915

415

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ006 w/62AQ060

920

418

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ006 w/62AQ100

935

425

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ007 w/62AQ060

995

452

95.6

2428.20

57.38

 

1457.30

42.12

 

1070

48HJ007 w/62AQ100

1010

459

95.6

2428.20

57.38

 

1457.30

42.12

 

1070

50HJ004 w/62AQ060

795

361

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ004 w/62AQ100

810

368

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ005 w/62AQ060

805

365

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ005 w/62AQ100

820

372

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ006 w/62AQ060

825

375

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ006 w/62AQ100

840

381

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ007 w/62AQ060

880

400

95.6

2428.20

57.38

 

1457.30

42.12

 

1070

50HJ007 w/62AQ100

895

407

95.6

2428.20

57.38

 

1457.30

42.12

 

1070

Fig. 6A — Rigging Label — COBRA™ Energy Recovery Unit — Sizes 48/50HJ004-007

Step 5 — Install Flue Hood (48HJ Rooftop Sec- tions Only) — Refer to the 48HJ installation instructions for information on installing the flue hood.

Step 6 — Install Gas Piping (48HJ Rooftop Sec- tions Only) — Refer to the 48HJ installation instructions for information on installing the gas piping.

Step 7 — Install External Trap For Condensate Drain — The condensate from the rooftop unit along with condensate from the upper coil of the energy recovery section is internally piped to the condensate pan in the lower section of the energy recovery section. For this reason, the bottom drain on the rooftop unit CANNOT be used for a condensate drain. The 3/4-in. drain connection on the energy recovery section is located near the bottom left of the exhaust air section. See Fig. 5A and 5B. The energy recovery section must have a field-fabricated, external, P-trap installed for condensate drain- age. Trap must be at least 4-in. deep to protect against freeze- up. If the drain line is installed downstream from the external

trap, pitch the line away from the unit at 1-in. per 10-ft of run. Do not use a pipe smaller than the connection (3/4-in.).

Step 8 — Make Electrical Connections

Unit cabinet must have an uninterrupted, unbroken electri- cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com- partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA, latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Fail- ure to follow this warning could result in the installer being liable for personal injury of others.

FIELD POWER SUPPLY — All units except 208/230-v units are factory wired for the voltage shown on the nameplate.

11

Page 11
Image 11
Carrier 48/50HJ004-014 specifications Make Electrical Connections, MAX Weight