Carrier 48/50HJ004-014 specifications Unoccupied, Occupied

Models: 48/50HJ004-014

1 44
Download 44 pages 2.92 Kb
Page 37
Image 37
UNOCCUPIED

Table 2 — Light Commercial Thermidistat (LCT) Operating Sequence and System Response

UNOCCUPIED

 

COOLING

ER Comp

 

ER Fans

 

 

RT Comp 1

 

RT Comp 2

 

RT Fans

 

RT Heat

Indoor Temperature Above 2nd Stage

 

 

 

 

 

 

 

 

 

 

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Low & OAT Low

On

 

On (cyc.)

 

 

On w/o MM

 

Off

 

On (cyc.)

 

Off

 

 

 

 

 

 

 

Humidity Low & OAT High

Off

 

Off

 

 

On w/o MM

 

w/o MM

 

On (cyc.)

 

Off

 

Humidity High & OAT Low

Off

 

Off

 

 

On w MM

 

On w MM

 

On (cyc.)

 

Off

 

Humidity High & OAT High

Off

 

Off

 

 

On w MM

 

On w MM

 

On (cyc.)

 

Off

Indoor Temperature Between 1st and

 

 

 

 

 

 

 

 

 

 

 

 

2nd Stage Set Points

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Low & OAT Low

Off

 

On (cyc.)

 

 

Off

 

Off

 

On (cyc.)

 

Off

 

 

 

 

 

 

 

Humidity Low & OAT High

Off

 

Off

 

 

On w/o MM

 

Off

 

On (cyc.)

 

Off

 

Humidity High & OAT Low

Off

 

Off

 

 

On w MM

 

Off

 

On (cyc.)

 

Off

 

Humidity High & OAT High

Off

 

Off

 

 

On w MM

 

Off

 

On (cyc.)

 

Off

Indoor Temperature Below 1st Stage

Off

 

Off

 

 

Off

 

Off

 

Off

 

Off

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: OAT < 55° all compression off*

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATING

ER Comp.

 

ER Fans

 

 

RT Comps.

 

RT Fans

 

RT Heat

 

 

Indoor Temperature Above 1st Set

Off

 

Off

 

 

Off

 

Off

 

Off

 

 

Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Temperature Between 1st and

Off

 

Off

 

 

Off

 

On (cyc.)

 

On, 50%

 

 

2nd Stage Set Points

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Temperature Below 2nd Stage

Off

 

Off

 

 

Off

 

On (cyc.)

 

On, 100%

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCCUPIED

 

 

 

 

 

 

 

 

 

 

COOLING

ER Comp

 

ER Fans

 

 

RT Comp 1

 

RT Comp 2

 

RT Fan

 

RT Heat

Indoor Temperature Above 2nd Stage

 

 

 

 

 

 

 

 

 

 

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Low & OAT Low

On

 

On

 

 

On w/o MM

 

On w/o MM

 

On

 

Off

 

 

 

 

 

 

 

Humidity Low & OAT High

On

 

On

 

 

On w/o MM

 

On w/o MM

 

On

 

Off

 

Humidity High & OAT Low

On

 

On

 

 

On w MM

 

On w MM

 

On

 

Off

 

Humidity High & OAT High

On

 

On

 

 

On w MM

 

On w MM

 

On

 

Off

Indoor Temperature Between 1st and

 

 

 

 

 

 

 

 

 

 

 

 

2nd Stage Set Points

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Low & OAT Low

Off

 

On

 

 

Off

 

Off

 

On

 

Off

 

 

 

 

 

 

 

Humidity Low & OAT High

On

 

On

 

 

On w/o MM

 

Off

 

On

 

Off

 

Humidity High & OAT Low

On

 

On

 

 

On w MM

 

Off

 

On

 

Off

 

Humidity High & OAT High

On

 

On

 

 

On w MM

 

Off

 

On

 

Off

Indoor Temperature Below 1st Stage

 

 

 

 

 

 

 

 

 

 

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Low

Off

 

On

 

 

Off

 

Off

 

On

 

Off

 

 

 

 

 

 

 

Humidity High

On

 

On

 

 

Off

 

Off

 

On

 

Off

NOTE: OAT < 55° all compression off*

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATING

ER Comp

 

ER Fans

 

 

RT Comps

 

RT Fans

 

RT Heat

 

 

Indoor Temperature Above 1st Stage

Off

 

On

 

 

Off

 

On

 

Off

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Temperature Between 1st and

 

 

 

 

 

 

 

 

 

 

 

 

2nd Stage Set Points

 

 

 

 

 

 

 

 

 

 

 

 

 

OAT >Set Pt

On

 

On

 

 

Off

 

On

 

Off

 

 

 

 

 

 

 

 

 

 

OAT <Set Pt

On

 

On

 

 

Off

 

On

 

On, 50%

 

 

Indoor Temperature Below 2nd Stage

 

 

 

 

 

 

 

 

 

 

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

OAT >Set Pt

On

 

On

 

 

Off

 

On

 

On, 50%

 

 

 

 

 

 

 

 

 

 

OAT <Set Pt

On

 

On

 

 

Off

 

On

 

On, 100%

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

Comp — Compressor

 

 

 

 

 

 

 

 

 

 

 

 

ER

Energy Recovery section

 

 

 

 

 

 

 

 

 

 

 

 

MMMoistureMi$er™ Dehumidification Device OAT — Outdoor-Air Temperature

RT — Rooftop Unit Set Pt — Set Point

*Unless unit compressor has been rewired as described in Step 11 (page 29).

37

Page 37
Image 37