Carrier 48/50HJ004-014 specifications Hood Top

Models: 48/50HJ004-014

1 44
Download 44 pages 2.92 Kb
Page 29
Image 29
HOOD TOP

Step 11 — Set the Outdoor Cooling and Heat- ing Thermostats

IMPORTANT: The energy recovery section unit is shipped with an outdoor thermostat set at 55 F which locks out mechanical cooling on the RTU (rooftop unit) and the energy recovery section compressor. If this feature is not desirable, the rooftop unit’s compressor can be allowed to run by relocating both gray wires to the same side of the Low Temperature Lockout Thermostat (LTLO) leaving the white wire on the opposite pole, locking out only the energy recovery section compressor. The LTLO is also accessible by removing the filter access panel and the door of the damper mounting bracket. Refer to Troubleshooting section.

COOLING — During the unoccupied period, the economizer mode of operation is used as the first stage of cooling. When the outside air temperature is below the cooling thermostat set point, the outside air will be used for first stage cooling.

HEATING — The heating thermostat should be adjusted to the second stage balance point (heat output of the energy re- covery section plus the heat output of the first stage on rooftop unit equals building load at this temperature). Above this set- ting, first stage heating will be the energy recovery section unit and second stage will be the first stage of the rooftop unit. Below this point first stage heating will be the energy recovery section unit plus first stage heating of the rooftop unit. The sec- ond stage will be the second stage of the rooftop unit.

HOOD TOP

DAMPER BLADE STOP

 

SHIPPED WITH UNIT

KNOB

IN 45° POSITION

SCREWS (2)

 

HOOD

 

SIDE

 

 

LTLO

 

MOUNTING

 

BRACKET

END CAP

HEATING POINT

THERMOSTAT

 

(RED LABEL)

 

COOLING SET POINT

 

 

THERMOSTAT (WHITE LABEL)

 

TEMPERATURE

 

 

 

 

COOLING

TEMPERATURE SWITCH

HOOD SIDE

LOCKOUT (LTLO)

 

 

 

SHIPPED WITH UNIT

SCREW INSTALLATION (2)

 

 

KNOB

 

ALUMINUM FILTER SCREEN

 

 

Fig. 11 — Energy Recovery Section Supply-Air Hood Assembly

HOOD TOP

HOOD SIDE

HINGE

HINGE PIN

BAROMETRIC

RELIEF DAMPER

60° LOCATION

45° LOCATIONManual background

HOOD SIDE

WIRE GUARD

30° LOCATION

DAMPER LIMITER

Fig. 12 — Energy Recovery Section Barometric Exhaust Air Hood Assembly

29

Page 29
Image 29
Carrier 48/50HJ004-014 specifications Hood Top