Carrier 48SS018-060 Ð Slab Mounting Details, Ð Suggested Rigging for Units Without, Base Rail

Models: 48SS018-060

1 52
Download 52 pages 6.1 Kb
Page 12
Image 12
Fig. 11 Ð Slab Mounting Details

Fig. 11 Ð Slab Mounting Details

NOTICE TO RIGGERS

Hook rigging shackles through holes in lifting brackets, as shown in Detail ``A.'' Lifting brackets to be centered around the unit center of gravity. Use wooden top skid when rigging, to prevent rigging straps from damaging unit.

All panels must be in place when rigging.

UNIT

MAX

A

 

 

B

C

 

48SS

WEIGHT

 

 

 

 

 

 

 

 

 

 

 

Size

lb

kg

in.

 

mm

in.

 

mm

in.

mm

018

332

150

 

 

 

24.3

 

618

24.85

631

024

375

170

 

 

 

22.4

 

570

24.85

631

030

384

174

 

 

 

22.3

 

565

24.85

631

036

408

185

49.4

 

1255

22.0

 

559

24.85

631

042

447

203

 

 

 

22.5

 

571

28.85

733

048

486

220

 

 

 

21.0

 

533

34.85

885

060

525

238

 

 

 

21.5

 

545

34.85

885

UNIT

 

 

 

 

 

 

 

 

 

 

48SX

 

 

 

 

 

 

 

 

 

 

024

405

184

 

 

 

22.8

 

579

28.9

733

030

408

185

 

 

 

22.4

 

569

28.9

733

036

438

199

49.4

 

1255

22.4

 

569

28.9

733

042

463

210

 

22.8

 

579

34.9

885

 

 

 

 

048

494

224

 

 

 

21.1

 

536

34.9

885

060

525

238

 

 

 

21.5

 

545

34.9

885

Fig. 12 Ð Suggested Rigging for Units Without

Base Rail

NOTICE TO RIGGERS

Hook rigging shackles through holes in lifting brackets, as shown in Detail ``A.'' Lifting brackets to be centered around the unit center of gravity. Use wood top skid when rigging, to prevent rigging straps from damaging unit. Remove 4 screws to slide wood support through rectangular hole in rail.

All panels must be in place when rigging.

UNIT

MAX

A

 

 

B

 

C

48SS

WEIGHT

 

 

 

 

 

 

 

 

 

 

 

 

Size

lb

kg

in.

 

mm

in.

 

mm

in.

 

mm

018

320

145

 

 

 

24.4

 

619

28.2

 

715

024

363

165

 

 

 

22.6

 

574

28.2

 

715

030

380

172

 

 

 

22.5

 

571

28.2

 

715

036

396

180

49.4

 

1255

22.2

 

563

28.2

 

715

042

435

197

 

 

 

22.6

 

574

32.2

 

816

048

474

215

 

 

 

21.2

 

538

38.2

 

969

060

513

233

 

 

 

21.6

 

549

38.2

 

969

UNIT

 

 

 

 

 

 

 

 

 

 

 

48SX

 

 

 

 

 

 

 

 

 

 

 

024

393

178

 

 

 

22.9

 

582

32.2

 

816

030

396

180

 

 

 

22.6

 

574

32.2

 

816

036

426

193

49.4

 

1255

22.5

 

571

32.2

 

816

042

451

205

 

22.9

 

582

38.2

 

969

 

 

 

 

 

048

482

219

 

 

 

21.3

 

540

38.2

 

969

060

513

233

 

 

 

21.6

 

549

38.2

 

969

Fig. 13 Ð Suggested Rigging for Units With

Optional Base Rail

UNITS WITHOUT BASE RAIL Ð If accessory rigging brackets are to be used for rigging, install them as follows:

Secure screws and paint protectors solidly against unit basepan to hold lifting brackets in position.

Never use lifting brackets when the temperature is be- low −10 F.

Never exceed 200 lbs per bracket of lifting force.

Never use lifting brackets for lifting other models of air- conditioning units.

Lifting point should be directly over the unit center of gravity.

1.Position brackets as close to the corners of unit as pos- sible. Be sure brackets are well outside of center of grav- ity. (See Fig. 2, 4, 6, 8, and 12.).

2.Position paint protectors and foam strips between screws and painted surface of unit. Tighten screws until they make contact with the paint protectors.

3.Secure device or hook of sufficient strength to hole in bracket as shown in detail ``A'' of Fig. 12.

4.If wood top is available, use it for a spreader bar to pre- vent straps from damaging unit. If wood top is not avail- able, use spreader bars of sufficient length.

12

Page 12
Image 12
Carrier 48SS018-060, 48SX024-060 Ð Slab Mounting Details, Ð Suggested Rigging for Units Without, Optional Base Rail