REQ'D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

Side opposite ducts

. .

. 36

(914)

Compressor access

. .

. 36

(914)

(Except for NEC requirements)

 

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

 

 

 

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts

.

. 14 (356)

Bottom of unit

. . . . . 0

Flue panel

.

. 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

Between units, control box side

 

. 42 (1067)

Unit and ungrounded surfaces, control box side

.

. 36 (914)

Unit and block or concrete walls and other grounded

 

 

surfaces, control box side

 

. 42 (1067)

 

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

UNIT

 

(lb/kg)

 

CHARACTERISTICS

 

 

 

 

 

 

lb

kg

A

B

C

D

48SX042060/080

208/230-1-60, 208/230-3-60, 460-3-60

391

178

100/45

91/41

120/55

80/36

48SX042100/120

208/230-1-60, 208/230-3-60, 460-3-60

403

183

103/47

94/43

123/56

83/38

48SX048080

208/230-1-60, 208/230-3-60, 460-3-60

422

192

109/50

85/39

158/72

70/32

48SX048100/120/140

208/230-1-60, 208/230-3-60, 460-3-60

434

197

112/51

88/40

161/73

73/33

48SX060080

208/230-1-60, 208/230-3-60

453

206

117/53

93/42

167/76

76/35

48SX060100/120/140

208/230-1-60, 208/230-3-60

465

211

120/55

96/44

167/76

82/37

 

 

 

 

 

 

 

 

UNIT

CENTER OF GRAVITY (in./mm)

X

Y

Z

 

48SX042060/080

26.66/677

21.19/538

15.35/390

48SX042100/120

26.61/676

21.21/539

15.35/390

48SX048080

28.45/723

19.95/507

15.35/390

48SX048100/120/140

28.35/720

19.99/508

15.35/390

48SX060080

28.36/720

23.27/591

15.35/390

48SX060100/120/140

27.95/710

23.23/590

15.35/390

 

 

 

 

 

 

LEGEND

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2.Adequate clearance around air openings into combustion chamber must be provided.

Fig. 8 Ð 48SX042-060 Without Base Rail, Unit Dimensions

8

Page 8
Image 8
Carrier 48SS018-060, 48SX024-060 user manual 48SX042-060 Without Base Rail, Unit Dimensions