Carrier 48SS018-060, 48SX024-060 user manual Electrical

Models: 48SS018-060

1 52
Download 52 pages 6.1 Kb
Page 6
Image 6
Manual background

REQ'D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

Side opposite ducts

. .

. 36

(914)

Compressor access

. .

. 36

(914)

(Except for NEC requirements)

 

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

 

 

 

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts

. . . . . . 14 (356)

Bottom of unit

. .

. .

. . . . . 0

Flue panel

. .

. .

. . 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

 

Between units, control box side

. . . . . 42 (1067)

Unit and ungrounded surfaces, control box side . . .

. .

. .

. . 36 (914)

Unit and block or concrete walls and other grounded

 

 

 

surfaces, control box side

. .

. .

. 42 (1067)

 

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

UNIT

 

(lb/kg)

 

CHARACTERISTICS

 

 

 

 

 

 

lb

kg

A

B

C

D

48SX024040

208/230-1-60

333

151

104/47

50/23

130/59

49/22

48SX024060

208/230-1-60

345

157

107/49

53/24

133/60

52/24

48SX030040

208/230-1-60

336

153

97/44

66/30

118/54

55/25

48SX030060/080

208/230-1-60

348

158

100/45

69/31

121/55

58/26

48SX036060/080

208/230-1-60, 208/230-3-60, 460-3-60

366

166

94/43

84/38

117/53

71/32

48SX036100/120

208/230-1-60, 208/230-3-60, 460-3-60

378

172

97/44

87/40

120/55

74/34

 

 

 

 

 

 

 

 

UNIT

CENTER OF GRAVITY (in./mm)

X

Y

Z

 

48SX024040

26.71/678

20.06/510

12.65/321

48SX024060

26.64/677

20.12/511

12.65/321

48SX030040

27.06/687

21.05/535

12.65/321

48SX030060/080

26.98/685

21.07/535

12.65/321

48SX036060/080

27.14/689

21.10/536

12.65/321

48SX036100/120

27.06/687

21.12/536

12.65/321

 

 

 

 

 

 

LEGEND

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2.Adequate clearance around air openings into combustion chamber must be provided.

Fig. 6 Ð 48SX024-036 Without Base Rail, Unit Dimensions

6

Page 6
Image 6
Carrier 48SS018-060, 48SX024-060 user manual Electrical