REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts | . . | . 36 | (914) |
Compressor access | . . | . 36 | (914) |
(Except for NEC requirements) |
|
|
|
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm) |
|
|
|
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts | . . . . . . 14 (356) | ||
Bottom of unit | . . | . . | . . . . . 0 |
Flue panel | . . | . . | . . 36 (914) |
NEC REQ'D CLEARANCES. in. (mm) |
|
|
|
Between units, control box side | . . . . . 42 (1067) | ||
Unit and ungrounded surfaces, control box side . . . | . . | . . | . . 36 (914) |
Unit and block or concrete walls and other grounded |
|
|
|
surfaces, control box side | . . | . . | . 42 (1067) |
| ELECTRICAL | UNIT WEIGHT |
| CORNER WEIGHT |
| ||
UNIT |
| (lb/kg) |
| ||||
CHARACTERISTICS |
|
|
|
| |||
|
| lb | kg | A | B | C | D |
48SX024040 | 333 | 151 | 104/47 | 50/23 | 130/59 | 49/22 | |
48SX024060 | 345 | 157 | 107/49 | 53/24 | 133/60 | 52/24 | |
48SX030040 | 336 | 153 | 97/44 | 66/30 | 118/54 | 55/25 | |
48SX030060/080 | 348 | 158 | 100/45 | 69/31 | 121/55 | 58/26 | |
48SX036060/080 | 366 | 166 | 94/43 | 84/38 | 117/53 | 71/32 | |
48SX036100/120 | 378 | 172 | 97/44 | 87/40 | 120/55 | 74/34 | |
|
|
|
|
|
|
|
|
UNIT | CENTER OF GRAVITY (in./mm) | |||
X | Y | Z | ||
| ||||
48SX024040 | 26.71/678 | 20.06/510 | 12.65/321 | |
48SX024060 | 26.64/677 | 20.12/511 | 12.65/321 | |
48SX030040 | 27.06/687 | 21.05/535 | 12.65/321 | |
48SX030060/080 | 26.98/685 | 21.07/535 | 12.65/321 | |
48SX036060/080 | 27.14/689 | 21.10/536 | 12.65/321 | |
48SX036100/120 | 27.06/687 | 21.12/536 | 12.65/321 | |
|
|
|
|
|
| LEGEND |
|
| |
CG | Ð | Center of Gravity | MAT'L | Ð | Material |
COND | Ð Condenser | NEC | Ð National Electrical Code | ||
LV | Ð | Low Voltage | REQ'D | Ð | Required |
NOTES:
1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.
2.Adequate clearance around air openings into combustion chamber must be provided.
Fig. 6 Ð 48SX024-036 Without Base Rail, Unit Dimensions