Carrier 48SX024-060, 48SS018-060 user manual Ð High- and Control-VoltageConnections

Models: 48SS018-060

1 52
Download 52 pages 6.1 Kb
Page 21
Image 21
Fig. 21 Ð High- and Control-Voltage Connections

LEGEND

Field Control-Voltage Wiring

Field High-Voltage Wiring

NOTE: Use blue wire for 3-phase units only.

Fig. 21 Ð High- and Control-Voltage Connections

Alternate Power Entry

1.Remove knockouts in ®xed compressor panel located on duct panel side of unit.

2.Route high-voltage leads into high-voltage terminal box.

3.Connect ground wire to green-yellow wire using ®eld- supplied splice.

4.Connect power wires to unit high-voltage leads.

5.On 3-phase units, locate blue wire projecting from com- pressor junction box. Cut wire at partition and route into high-voltage junction box through grommet in back of junction box.

6.On 3-phase units, strip back blue lead and connect to third leg of the power wires.

SPECIAL PROCEDURES FOR 208-V OPERATION

Make sure that the gas supply then the power supply to the unit is switched OFF before making any wiring changes. Electrical shock can cause personal injury or death.

1.Disconnect the orange transformer-primary lead from the contactor. See unit wiring label.

2.Remove the tape and wirenut from the terminal on the end of the red transformer-primary lead.

3.Save the wirenut.

4.Connect the red lead to the contactor terminal from which the orange lead was disconnected.

5.Using the wirenut removed from the red lead, insulate the loose terminal on the orange lead.

6.Wrap the cover with electrical tape so that the metal ter- minal cannot be seen.

CONTROL VOLTAGE CONNECTIONS; NON- INTEGRATED CONTROL MOTOR (NON-ICM) UNITS

ÐLocate the room thermostat on an inside wall in the space to be conditioned, where it will not be subjected to either a cooling or heating source or direct exposure to sunlight. Mount the thermostat 4 to 5 ft above the ¯oor.

NOTE: Do not use any type of power-stealing thermostat. Unit control problems may result.

Use no. 18 American Wire Gage (AWG) color-coded, in- sulated (35 C minimum) wires to make the control voltage connections between the thermostat and the unit. If the ther- mostat is located more than 100 ft from the unit (as mea- sured along the control voltage wires), use no. 16 AWG color- coded, insulated (35 C minimum) wires.

Standard Connection Ð Remove knockout hole located in the ¯ue panel adjacent to the control access panel. See Fig. 2-9. Remove the rubber grommet from the installer's packet (included with unit) and install grommet in the knock- out opening. Provide a drip loop before running wire through panel.

Run the low-voltage leads from the thermostat, through the inlet hole, and into unit low-voltage splice box.

Locate ®ve 18-gage wires leaving control box. These low- voltage connection leads can be identi®ed by the colors red, green, yellow, brown, and white. (See Fig. 21.) Ensure the leads are long enough to be routed into the low-voltage splice box (located below right side of control box). Cut wires at the point where they exit control box; do NOT cut yellow wire on 48SX024,030 units. Stripped yellow wire is located in connection box. Route leads through hole in bottom of control box and make low-voltage connections as shown in Fig. 21. Secure all cut wires, so that they do not interfere with operation of unit.

Alternate Connection Ð Remove knockout in compressor fixed panel located below high-voltage knockout. Remove the rub- ber grommet from the installer's packet (included with unit) and install grommet in the knockout opening. Route ther- mostat wires through grommet providing drip loop at panel. Connect low-voltage leads as shown in Fig. 21. On 48SX024 and 030 units, the yellow wire originating from discharge thermostat of compressor must be cut and routed into low- voltage section of junction box.

CONTROL VOLTAGE CONNECTIONS; INTEGRATED CONTROL MOTOR (ICM) UNITS

Routing Control Power Wires (24 v) Ð Remove knockout in the compressor ®xed access panel located below the high- voltage knockout. Remove the rubber grommet from the in- staller's packet (included with unit) and install grommet in the knockout opening. Route thermostat wires through grom- met providing drip loop at panel. Connect low-voltage leads to the thermostat.

Alternate Connection (24 v) Ð Remove knockout in the flue panel adjacent to the control access panel. Remove the rub- ber grommet from the installer's packet (included with unit) and install grommet in the knockout opening. Provide a drip loop before running wire through panel. Run the low- voltage leads from the thermostat, through the inlet hole, and into the unit low-voltage splice box.

Connecting to Easy Select Interface Board Ð The Easy Se- lect interface board is located in the control box area. The Easy Select interface board is factory wired to the motor, and factory default selections are preset.

Locate the ®ve 18-gage thermostat lead wires of plug as- sembly 1 (PL1) attached to the Easy Select interface board (See Fig. 22 and wiring diagrams for units 48SX048 and 060 on pages 31 and 33.) These low voltage connection leads are identi®ed by the colors red, green, yellow, brown, and white. Cut the wires between the 2 wire ties approximately 4 in. from the plug. Connect low-voltage leads to the ther- mostat. Secure all cut wires in the control and splice boxes so they do not interfere with the proper operation of the unit.

21

Page 21
Image 21
Carrier 48SX024-060, 48SS018-060 user manual Ð High- and Control-VoltageConnections