Carrier 48SX024-060, 48SS018-060 user manual REQD CLEARANCES FOR SERVICING. in. mm

Models: 48SS018-060

1 52
Download 52 pages 6.1 Kb
Page 7
Image 7
Manual background

REQ'D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 Unit top . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914) Side opposite ducts . . . . . . . . . . . . . . . . . . . . 36 (914) Compressor access . . . . . . . . . . . . . . . . . . . . 36 (914) (Except for NEC requirements)

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

Maximum extension of overhangs . . . . . . . . . . . . . 48 (1219)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct side of unit . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts . . . . . . . . . . . . . . . . . . . . 14 (356)

Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . 0

Flue panel . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

Between units, control box side

. 42

(1067)

Unit and ungrounded surfaces, control box side

. . 36 (914)

Unit and block or concrete walls and other grounded

 

 

surfaces, control box side

. 42

(1067)

 

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

UNIT

 

(lb/kg)

 

CHARACTERISTICS

 

 

 

 

 

 

lb

kg

A

B

C

D

48SX024040

208/230-1-60

357

163

110/50

56/25

136/62

55/25

48SX024060

208/230-1-60

369

168

113/51

59/27

139/63

58/26

48SX030040

208/230-1-60

360

164

103/47

72/33

124/56

61/28

48SX030060/080

208/230-1-60

372

169

106/48

75/34

127/58

64/29

48SX036060/080

208/230-1-60, 208/230-3-60, 460-3-60

390

177

100/45

90/41

123/56

77/35

48SX036100/120

208/230-1-60, 208/230-3-60, 460-3-60

402

183

103/47

93/42

127/57

80/36

 

 

 

 

 

 

 

 

UNIT

CENTER OF GRAVITY (in./mm)

X

Y

Z

 

48SX024040

26.57/674.9

20.17/512.3

14.96/380.0

48SX024060

26.51/673.3

20.22/513.6

14.96/380.0

48SX030040

26.90/683.3

21.09/535.7

14.96/380.0

48SX030060/080

26.83/681.5

21.11/536.2

14.96/380.0

48SX036060/080

26.99/685.5

21.14/537.0

14.96/380.0

48SX036100/120

26.92/683.8

21.14/537.0

14.96/380.0

 

 

LEGEND

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2.Adequate clearance around air openings into combustion chamber must be provided.

Fig. 7 Ð 48SX024-036 With Optional Base Rail, Unit Dimensions

7

Page 7
Image 7
Carrier 48SX024-060, 48SS018-060 user manual REQD CLEARANCES FOR SERVICING. in. mm