Table 2 Ð Physical Data Ð Unit 48SX

UNIT SIZE 48SX

 

024040

024060

030040

030060

 

030080

 

036060

036080

036100

036120

NOMINAL CAPACITY (ton)

 

2

 

2

21¤2

21¤2

 

21¤2

 

 

3

 

3

 

3

 

3

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Without Base Rail

 

333

345

336

348

 

348

 

366

366

378

378

With Optional Base Rail

357

369

360

372

 

372

 

390

390

402

402

COMPRESSORS

 

 

 

 

 

 

 

 

 

 

Scroll

 

 

 

 

 

 

 

 

Quantity

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

REFRIGERANT (R-22)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charge (lb)

 

 

3.9

 

3.9

 

4.5

 

4.5

 

 

4.5

 

 

5.4

 

5.4

 

5.4

 

5.4

REFRIGERANT METERING DEVICE

 

 

 

 

 

 

 

 

Acutrol™ Device

 

 

 

 

 

 

 

 

Ori®ce ID (in.)

 

.034

.034

.030

.030

 

.030

 

.032

.032

.032

.032

CONDENSER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

 

2

...17

2

...17

2

...17

2...

17

 

2...

17

 

2...

17

2...

17

2...

17

2...

17

Face Area (sq ft)

 

 

7.0

 

7.0

 

7.0

 

7.0

 

 

7.0

 

 

7.0

 

7.0

 

7.0

 

7.0

CONDENSER FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Cfm

 

2200

2200

2200

2200

 

2200

 

2200

2200

2200

2200

Diameter (in.)

 

 

20

 

20

 

20

 

20

 

 

20

 

 

20

 

20

 

20

 

20

Motor Hp (Rpm)

 

1¤4 (1100)

1¤4 (1100)

1¤4 (1100)

1¤4 (1100)

 

1¤4 (1100)

 

1¤4 (1100)

1¤4 (1100)

1¤4 (1100)

1¤4 (1100)

EVAPORATOR COIL

 

2

...15

2...

15

3...

15

3...

15

 

3...

15

 

4...

15

4...

15

4...

15

4...

15

Rows Fins/in.

 

 

 

Face Area (sq ft)

 

 

3.6

 

3.6

 

2.7

 

2.7

 

 

2.7

 

 

3.6

 

3.6

 

3.6

 

3.6

EVAPORATOR FAN*

 

 

 

 

 

 

 

 

 

 

Direct Drive

 

 

 

 

 

 

 

 

Nominal Air¯ow (Cfm)

800

800

1000

1000

 

1000

 

1200

1200

1200

1200

Size (in.)

 

10 x 10

10 x 10

10 x 10

10 x 10

 

10 x 10

 

10 x 10

10 x 10

10 x 10

10 x 10

Motor Hp

 

 

1¤4

 

1¤4

 

1¤4

 

1¤4

 

 

1¤4

 

 

1¤2

 

1¤2

 

1¤2

 

1¤2

FURNACE SECTION²

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Burner Ori®ce (Qty...

drill size)

1

...32

2

...40

1

...32

2

...40

 

2

...32

 

2...

40

2...

32

2...

30

3...

32

Natural Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Burner Ori®ce (Qty...

drill size)

1

...41

2

...47

1

...41

2

...47

 

2

...42

 

2...

47

2...

42

2...

40

3...

42

Propane Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETURN-AIR FILTERS (in.)**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disposable

 

24 x 24

24 x 24

24 x 24

24 x 24

 

24 x 24

 

24 x 24

24 x 24

24 x 24

24 x 24

UNIT SIZE 48SX

 

042060

042080

042100

042120

048080

048100

048120

048140

060080

060100

060120

060140

NOMINAL CAPACITY (ton)

31¤2

31¤2

31¤2

31¤2

 

4

 

4

 

4

 

4

 

5

 

5

 

5

 

5

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Without Base Rail

 

391

391

403

403

422

434

434

434

453

465

465

465

With Optional Base Rail

415

415

427

427

446

458

458

458

477

489

489

489

COMPRESSORS

 

 

 

 

 

 

 

 

 

 

 

 

Scroll

 

 

 

 

 

 

 

 

 

 

 

Quantity

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT (R-22)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charge (lb)

 

 

5.7

 

5.7

 

5.7

 

5.7

 

5.8

 

5.8

 

5.8

 

5.8

7.00

7.00

7.00

7.00

REFRIGERANT METERING

 

 

 

 

 

 

 

 

 

 

Acutrol Device

 

 

 

 

 

 

 

 

 

 

DEVICE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ori®ce ID (in.)

 

.034

.034

.034

.034

.034

.034

.034

.034

.030

.030

.030

.030

CONDENSER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

 

2

...17

2

...17

2

...17

2

...17

2

...17

2

...17

2

...17

2

...17

2

...17

2

...17

2

...17

2

...17

Face Area (sq ft)

 

 

8.7

 

8.7

 

8.7

 

8.7

 

8.7

 

8.7

 

8.7

 

8.7

8.67

8.67

8.67

8.67

CONDENSER FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Cfm

 

2400

2400

2400

2400

2400

2400

2400

2400

2400

2400

2400

2400

Diameter (in.)

 

 

20

 

20

 

20

 

20

 

20

 

20

 

20

 

20

 

20

 

20

 

20

 

20

Motor Hp (Rpm)

 

1¤4 (1100)

1¤4 (1100)

1¤4 (1100)

1¤4 (1100)

1¤4 (1100)

1¤4 (1100)

1¤4 (1100)

1¤4 (1100)

1¤3 (1050)

1¤3 (1050)

1¤3 (1050)

1¤3 (1050)

EVAPORATOR COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows Fins/in.

 

3

...15

3

...15

3

...15

3

...15

4

...15

4

...15

4

...15

4

...15

4...

15

4...

15

4...

15

4...

15

Face Area (sq ft)

 

 

4.4

 

4.4

 

4.4

 

4.4

 

4.4

 

4.4

 

4.4

 

4.4

4.44

4.44

4.44

4.44

EVAPORATOR FAN*

 

 

 

 

 

 

 

 

 

 

 

Direct Drive

 

 

 

 

 

 

 

 

 

 

Nominal Air¯ow (Cfm)

1400

1400

1400

1400

1600

1600

1600

1600

1995

1995

1995

1995

Size (in.)

 

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

10 x 11

10 x 11

10 x 11

10 x 11

Motor Hp

 

 

3¤4

 

3¤4

 

3¤4

 

3¤4

 

3¤4

 

3¤4

 

3¤4

 

3¤4

 

1

 

1

 

1

 

1

FURNACE SECTION²

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Burner Ori®ce (Qty...

drill size)

2

...40

2

...32

2

...30

3

...32

2

...32

2

...30

3

...32

3

...31

2

...32

2

...30

3

...32

3...

31

Natural Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Burner Ori®ce (Qty...

drill size)

2

...47

2

...42

2

...40

3

...42

2

...42

2

...40

3

...42

3

...40

3

...42

2

...40

3

...42

3...

40

Propane Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETURN-AIR FILTERS (in.)**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disposable

 

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

24 x 30

*Size 048 evaporator fan is equipped with a 460-v or integrated control motor (ICM). Size 060 evaporator fan is equipped with an ICM only. The ICM provides variable speed.

²Based on an altitude of 0-2000 feet.

**Required ®lter sizes shown are based on the ARI (Air Conditioning & Refrigeration Institute) rated heating air¯ow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity type. For non-standard air ®lters, air ®lter pressure drop must not exceed 0.08 in. wg.

15

Page 15
Image 15
Carrier 48SX024-060, 48SS018-060 user manual Physical Data Ð Unit 48SX, Unit Size 48SX