Carrier 48SS018-060, 48SX024-060 user manual Electrical

Models: 48SS018-060

1 52
Download 52 pages 6.1 Kb
Page 2
Image 2
ELECTRICAL

REQ'D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

Side opposite ducts

. .

. 36

(914)

Compressor access

. .

. 36

(914)

(Except for NEC requirements)

 

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

 

 

 

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts

.

. 14 (356)

Bottom of unit

. . . . . 0

Flue panel

.

. 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

Between units, control box side

 

. 42 (1067)

Unit and ungrounded surfaces, control box side

.

. 36 (914)

Unit and block or concrete walls and other grounded

 

 

surfaces, control box side

 

. 42 (1067)

 

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

UNIT HEIGHT

UNIT

 

(lb/kg)

 

(in./mm)

CHARACTERISTICS

 

 

 

 

 

 

lb

kg

A

B

C

D

E

48SS180040

208/230-1-60

272

123

81/37

62/28

76/35

53/24

24.1/613

48SS024040

208/230-1-60

303

138

97/44

43/20

123/56

40/18

24.1/613

48SS024060

208/230-1-60

315

143

100/45

46/21

126/57

43/20

24.1/613

48SS030040

208/230-1-60, 208/230-3-60

320

145

100/45

47/21

126/57

47/21

24.1/613

48SS030060/080

208/230-1-60, 208/230-3-60

332

149

103/46

50/22

129/58

50/23

24.1/613

48SS036060/080

208/230-1-60, 208/230-3-60, 460-3-60

336

153

86/39

76/35

111/50

63/29

24.1/613

48SS036100/120

208/230-1-60, 208/230-3-60, 460-3-60

348

158

89/40

79/36

114/52

66/30

24.1/613

48SS042060/080

208/230-1-60, 208/230-3-60, 460-3-60

375

170

95/43

86/39

119/54

75/34

28.1/714

48SS042100/120

208/230-1-60, 208/230-3-60, 460-3-60

387

176

98/45

89/40

122/55

78/35

28.1/714

 

 

 

 

 

 

 

 

 

UNIT

F

G

CENTER OF GRAVITY in./mm

 

in./mm

in./mm

X

Y

Z

48SS018040

 

 

25.07/637

20.59/523

 

48SS024040

 

 

27.07/688

23.35/593

 

48SS024060

 

 

26.98/685

23.27/591

 

48SS030040

169¤16/420.7

1815¤16/481.0

26.71/678

23.46/596

10.85/276

48SS030060/080

 

 

27.15/689

22.36/568

 

48SS036060/080

 

 

27.50/698

22.48/571

 

48SS036100/120

 

 

27.40/696

22.44/570

 

48SS042060/080

209¤16/522.3

2215¤16/582.6

27.01/686

22.44/570

12.7/321

48SS042100/120

26.94/684

22.44/570

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2.Adequate clearance around air openings into combustion chamber must be provided.

Fig. 2 Ð 48SS018-042 Without Base Rail, Unit Dimensions

2

Page 2
Image 2