Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . .
·ROOF CURB
·ALTERNATE UNIT SUPPORT
Step 2 Ð Rig and Place Unit . . . . . . . . . . . . . . . . . 8
·POSITIONING
·ROOF MOUNT
Step 3 Ð Field Fabricate Ductwork . . . . . . . . . . . 11 Step 4 Ð Make Unit Duct Connections . . . . . . . 11 Step 5 Ð Trap Condensate Drain . . . . . . . . . . . . . 11 Step 6 Ð Controls Options . . . . . . . . . . . . . . . . . . 12
·CONSTANT VOLUME APPLICATIONS
·VARIABLE AIR VOLUME (VAV)
APPLICATIONS
Step 7 Ð Make Electrical Connections . . . . . . . 15
·POWER WIRING
·FIELD POWER SUPPLY
·FIELD CONTROL WIRING
Step 8 Ð Make
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
·ECONOMIZER
·ECONOMIZER SETTINGS
Step 9 Ð Position Power Exhaust/
Barometric Relief Damper Hood . . . . . . . . . . . . . 29 Step 10 Ð Install Accessories . . . . . . . . . . . . . . . 30
IMPORTANT Ð READ BEFORE INSTALLING
IMPORTANT: Due to upgrades in unit control soft- ware and hardware, units produced currently are slightly different than original design units. The unit control software (which has changed) is designated with a sticker on the unit control board, chip U8 (the large chip in the center of the board), which states the software Ver- sion number. Version 1.0 is the original version. Ver- sion 2.0 is the current version. Differences in instal- lation, con®guration, and
INSTALLATION
Step 1 Ð Provide Unit Support
All panels must be in place when rigging. Unit is not designed for handling by fork truck.
ROOF CURB Ð Assemble and install accessory roof curb in accordance with instructions shipped with the curb. Ac- cessory roof curb and information required to ®eld fabricate a roof curb or horizontal adapter are shown in Fig. 1 and 2. Install insulation, cant strips, roo®ng, and counter ¯ashing as shown. Ductwork can be secured to roof curb before unit is set in place.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a
SAFETY CONSIDERATIONS
Installation and servicing of
Untrained personnel can perform basic maintenance func- tions of cleaning coils and ®lters and replacing ®lters. All other operations should be performed by trained service per- sonnel. When working on
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have ®re ex- tinguishers available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
Curb should be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is shown in Fig 1 and 2. Refer to Accessory Roof Curb Installation In- structions for additional information as required. When ac- cessory roof curb is used, unit may be installed on class A, B, or C roof covering material.
ALTERNATE UNIT SUPPORT Ð When the curb or adapter cannot be used, support unit with sleepers using unit curb or adapter support area. If sleepers cannot be used, support long sides of unit (refer to Fig.
Manufacturer reserves the right to discontinue, or change at any time, speci®cations or designs without notice and without incurring obligations.