Table 14 Ð Fan Performance, 50EJ048 Ð Vertical Discharge Units
FOR EW UNITS, REDUCE NET AVAILABLE EXTERNAL STATIC PRESSURE BY 0.5 IN. WG
AIRFLOW |
|
|
|
|
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
|
| |||||||||||||||||
0.2 |
|
|
| 0.4 |
|
|
|
| 0.6 |
| 0.8 |
| 1.0 |
|
|
| 1.2 |
|
| 1.4 |
| 1.6 | ||||||||||||
(Cfm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||
| Rpm |
| Bhp |
| Rpm |
|
| Bhp | Rpm |
| Bhp |
| Rpm |
| Bhp | Rpm |
|
| Bhp |
| Rpm |
| Bhp | Rpm |
| Bhp | Rpm |
| Bhp | |||||
13,000 | 683 | 7.10 |
| 715 |
|
| 8.59 | 747 |
| 9.09 |
| 777 | 9.60 | 808 |
|
| 10.11 |
| 837 |
| 10.62 | 866 |
| 11.14 | 894 |
| 11.66 | |||||||
14,000 | 730 | 8.53 |
| 761 |
| 10.25 | 790 |
| 10.77 |
| 819 | 11.30 | 847 |
|
| 11.83 |
| 875 |
| 12.36 | 902 |
| 12.90 | 929 |
| 13.44 | ||||||||
15,000 | 778 | 10.14 |
| 807 |
| 12.10 | 834 |
| 12.65 |
| 862 | 13.19 | 888 |
|
| 13.75 |
| 915 |
| 14.30 | 941 |
| 14.86 | 966 |
| 15.42 | ||||||||
16,000 | 826 | 11.93 |
| 853 |
| 14.15 | 879 |
| 14.72 |
| 905 | 15.29 | 931 |
|
| 15.86 |
| 955 |
| 16.44 | 980 |
| 17.01 | 1004 |
| 17.59 | ||||||||
17,000 | 875 | 13.90 |
| 900 |
| 16.42 | 925 |
| 17.01 |
| 949 | 17.60 | 973 |
|
| 18.19 |
| 997 |
| 18.78 | 1020 |
| 19.38 | 1043 |
| 19.98 | ||||||||
18,000 | 923 | 16.06 |
| 947 |
| 18.90 | 971 |
| 19.51 |
| 994 | 20.12 | 1017 |
|
| 20.73 |
| 1039 |
| 21.34 | 1062 |
| 21.96 | 1084 |
| 22.58 | ||||||||
19,000 | 972 | 18.42 |
| 995 |
| 21.61 | 1017 |
| 22.24 |
| 1039 | 22.87 | 1061 |
|
| 23.50 |
| 1083 |
| 24.13 | 1104 |
| 24.76 | 1125 |
| 25.40 | ||||||||
20,000 | 1021 | 20.98 |
| 1042 |
| 24.55 | 1064 |
| 25.20 |
| 1085 | 25.85 | 1106 |
|
| 26.50 |
| 1126 |
| 27.15 | 1147 |
| 27.80 | 1167 |
| 28.46 | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
AIRFLOW |
|
|
|
|
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
|
| |||||||||||||||||
1.8 |
|
|
| 2.0 |
|
|
|
| 2.2 |
| 2.4 |
| 2.6 |
|
|
| 2.8 |
|
| 3.0 |
| 3.2 | ||||||||||||
(Cfm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||
| Rpm |
| Bhp |
| Rpm |
|
| Bhp | Rpm |
| Bhp |
| Rpm |
| Bhp | Rpm |
|
| Bhp |
| Rpm |
| Bhp | Rpm |
| Bhp | Rpm |
| Bhp | |||||
13,000 | 921 | 12.18 |
| 948 |
| 12.71 | 975 |
| 13.24 |
| 1001 | 13.77 | 1026 |
|
| 14.30 |
| 1051 |
| 14.84 | 1076 |
| 15.39 | 1100 |
| 15.93 | ||||||||
14,000 | 955 | 13.98 |
| 981 |
| 14.53 | 1006 |
| 15.08 |
| 1031 | 15.63 | 1056 |
|
| 16.18 |
| 1080 |
| 16.74 | 1103 |
| 17.30 | 1127 |
| 17.86 | ||||||||
15,000 | 991 | 15.98 |
| 1015 |
| 16.54 | 1040 |
| 17.11 |
| 1063 | 17.68 | 1087 |
|
| 18.25 |
| 1110 |
| 18.83 | 1133 |
| 19.41 | 1155 |
| 19.99 | ||||||||
16,000 | 1028 | 18.17 |
| 1051 |
| 18.76 | 1074 |
| 19.34 |
| 1097 | 19.93 | 1120 |
|
| 20.52 |
| 1142 |
| 21.12 | 1164 |
| 21.71 | 1185 |
| 22.31 | ||||||||
17,000 | 1066 | 20.58 |
| 1089 |
| 21.18 | 1111 |
| 21.78 |
| 1133 | 22.39 | 1154 |
|
| 23.00 |
| 1175 |
| 23.61 | 1197 |
| 24.23 | Ð |
| Ð | ||||||||
18,000 | 1106 | 23.19 |
| 1127 |
| 23.82 | 1148 |
| 24.44 |
| 1169 | 25.07 | 1190 |
|
| 25.69 |
| Ð |
| Ð |
| Ð |
| Ð | Ð |
| Ð | |||||||
19,000 | 1146 | 26.04 |
| 1166 |
| 26.68 | 1187 |
| 27.32 |
| Ð | Ð | Ð |
| Ð | Ð |
| Ð |
|
| Ð |
| Ð | Ð |
| Ð | ||||||||
20,000 | 1187 | 29.11 |
| Ð |
|
| Ð |
| Ð |
|
| Ð | Ð | Ð | Ð | Ð |
|
| Ð |
| Ð |
|
|
| Ð |
| Ð | Ð |
| Ð | ||||
|
|
|
|
|
|
|
|
|
| LEGEND |
|
|
|
|
|
|
|
|
|
| ||||||||||||||
AIRFLOW | AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||||
| 3.4 |
|
|
|
|
| 3.6 |
|
| 3.6 |
|
| Bhp Ð |
| Brake Horsepower |
|
|
|
|
|
| |||||||||||||
(Cfm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
| Rpm |
| Bhp |
| Rpm |
| Bhp |
| Rpm |
| Bhp |
| NOTES: |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
13,000 | 1124 |
| 16.48 |
| 1148 |
| 17.03 |
| 1171 |
| 17.59 | 1. | Fan performance is based on wet coils, economizer, roof curb, | |||||||||||||||||||||
14,000 | 1150 |
| 18.43 |
| 1173 |
| 19.00 |
| 1195 |
| 19.57 |
|
| cabinet losses, and clean |
|
|
| |||||||||||||||||
15,000 | 1177 |
| 20.57 |
| 1199 |
| 21.16 |
| Ð |
| Ð | 2. | Conversion − Bhp to watts: |
|
|
|
|
|
| |||||||||||||||
16,000 | Ð |
| Ð |
|
| Ð |
|
|
| Ð | Ð | Ð |
|
|
|
|
|
|
|
| Bhp x 746 |
|
|
|
|
|
| |||||||
17,000 | Ð |
| Ð |
|
| Ð |
|
|
| Ð | Ð | Ð |
|
|
|
| Watts = |
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
| Motor efficiency |
|
|
|
|
|
| |||||||||||||||||
18,000 | Ð |
| Ð |
|
| Ð |
|
|
| Ð | Ð | Ð |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
19,000 | Ð |
| Ð |
|
| Ð |
|
|
| Ð | Ð | Ð |
|
|
| 3. VAV units will operate down to 70 cfm/ton. |
|
|
| |||||||||||||||
20,000 | Ð |
| Ð |
|
| Ð |
|
|
| Ð | Ð | Ð |
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table 15 Ð Air Quantity Limits
UNIT | MINIMUM HEATING | MINIMUM COOLING | MINIMUM COOLING | MAXIMUM |
50EJ,EK,EW,EY | CFM | CFM (VAV) | CFM (CV) | CFM |
024 | 6,000 | 2000 | 6,000 | 10,000 |
028 | 7,500 | 2500 | 7,500 | 12,500 |
030 | 8,250 | 2750 | 8,250 | 13,750 |
034 | 9,000 | 3000 | 9,000 | 15,000 |
038 | 10,500 | 3500 | 10,500 | 17,500 |
044 | 12,000 | 4000 | 12,000 | 20,000 |
048 | 13,500 | 4500 | 13,500 | 22,500 |
|
|
|
|
|
LEGEND
CV Ð Constant Volume
VAV Ð Variable Air Volume
38