Carrier 50EK, 50EJ, 50EW, 50EY installation instructions Ð Motor Limitations, Ð User Dened Set Points

Models: 50EK 50EY 50EW 50EJ

1 56
Download 56 pages 61.69 Kb
Page 39
Image 39
Table 16 Ð Motor Limitations

Table 16 Ð Motor Limitations

STANDARD EFFICIENCY MOTORS

Nominal

Maximum

 

 

Maximum Amps

 

 

Maximum

Motor

Hp

Bhp

208

230

460

575

Watts

Efficiency

5

5.9

17.94

16.99

Ð

Ð

5,348

82.3

5.9

Ð

Ð

8.50

5.78

5,240

84.0

 

7.5

8.7

25.52

24.36

Ð

Ð

7,717

84.1

9.5

Ð

Ð

13.30

9.63

8,549

82.9

 

10

10.2

26.93

25.50

Ð

Ð

8,879

85.7

11.8

Ð

Ð

14.75

11.33

10,284

85.6

 

15

15.3

42.84

40.80

Ð

Ð

13,686

83.4

18.0

Ð

Ð

24.00

18.00

15,891

84.5

 

20

22.4

59.36

56.00

Ð

Ð

19,032

87.8

23.4

Ð

Ð

29.25

22.82

19,950

87.5

 

25

28.9

76.30

72.83

Ð

Ð

24,499

88.0

29.4

Ð

Ð

37.04

28.69

25,181

87.1

 

30

35.6

92.56

87.81

Ð

Ð

29,378

90.4

34.7

Ð

Ð

42.80

 

n/a

29,316

88.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH EFFICIENCY MOTORS

 

 

 

 

 

 

 

 

 

Nominal

Maximum

 

 

Maximum Amps

 

 

Maximum

Motor

Hp

Bhp

208

 

230

 

460

 

575

Watts

Efficiency

 

5.9

16.76

 

13.92

 

Ð

 

Ð

5,030

87.5

5

5.9

Ð

 

Ð

 

6.96

 

Ð

5,030

87.5

 

5.9

Ð

 

Ð

 

Ð

 

5.66

4,918

89.5

 

8.7

26.10

 

22.27

 

Ð

 

Ð

7,334

88.5

7.5

9.5

Ð

 

Ð

 

12.16

 

Ð

8,008

88.5

 

9.5

Ð

 

Ð

 

Ð

 

9.50

7,728

91.7

 

10.2

28.56

 

24.89

 

Ð

 

Ð

8,502

89.5

10

11.8

Ð

 

Ð

 

14.40

 

Ð

9,836

89.5

 

11.8

Ð

 

Ð

 

Ð

 

11.68

9,600

91.0

 

15.3

45.08

 

39.17

 

Ð

 

Ð

12,543

91.0

15

18.0

Ð

 

Ð

 

23.04

 

Ð

14,756

91.0

 

18.0

Ð

 

Ð

 

Ð

 

18.12

14,439

93.0

 

22.4

63.84

 

55.55

 

Ð

 

Ð

18,363

91.0

20

23.4

Ð

 

Ð

 

29.02

 

Ð

19,183

91.0

 

23.4

Ð

 

Ð

 

Ð

 

23.17

18,650

93.6

 

28.9

80.69

 

70.05

 

Ð

 

Ð

23,511

91.7

25

29.4

Ð

 

Ð

 

35.63

 

Ð

23,918

91.7

 

29.4

Ð

 

Ð

 

Ð

 

28.81

23,432

93.6

 

35.6

102.65

 

89.00

 

Ð

 

Ð

28,742

92.4

30

34.7

Ð

 

Ð

 

43.38

 

Ð

28,015

92.4

 

34.7

Ð

 

Ð

 

Ð

 

33.89

27,656

93.6

 

 

 

 

 

 

 

 

 

 

 

LEGEND

BHP Ð Brake Horsepower

NOTE: Extensive motor and electrical testing on the Carrier units has ensured that the full horsepower range of the motor can be utilized with con®dence. Using your fan motors up to the horsepower ratings shown on the Motor Limi- tations table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

Table 17 Ð User De®ned Set Points

 

SET POINT

 

FORMAT

DESCRIPTION

LIMITS

DEFAULT

 

 

OHSP

 

xx.xF

Occupied Heat Set Point

55 to 80 F

68

 

 

OCSP

 

xx.xF

Occupied Cool Set Point

55 to 80 F

78

 

 

UHSP

 

xx.xF

Unoccupied Heat Set Point

40 to 80 F

55

 

 

UCSP

 

xx.xF

Unoccupied Cool Set Point

75 to 95 F

90

 

 

SASP

 

xx.xF

Supply Air Set Point

45 to 70 F

55

 

 

OATL

 

xx.xF

Hi OAT Lockout Temperature

55 to 75 F

65

 

 

NTLO

 

xx.xF

Unoccupied OAT Lockout Temperature

40 to 70 F

50

 

 

RTIO

 

xx.x

Reset Ratio

0 to 10

3

 

 

LIMT

 

xx.x^F

Reset Limit

0 to 20 F

10

 

 

MDP

 

xxx%

Minimum Damper Position

0 to 100%

20

 

 

IAQS

 

xxxx

IAQ Set Point

1 to 5000

650

 

 

UHDB

 

xx.x^F

Unoccupied Heating Deadband

0 to 10

1

 

 

UCDB

 

xx.x^F

Unoccupied Cooling Deadband

0 to 10

1

 

 

LTMP

 

xx.xF

Low Temp. Min. Position

0 to 100

10

 

 

HTMP

 

xx.xF

High Temp. Min. Position

0 to 100

35

 

 

PES1

 

xx.xF

CV Power Exhaust Stage 1 Point

0 to 100

25

 

 

PES2

 

xx.xF

CV Power Exhaust Stage 2 Point

0 to 100

75

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

CV

Ð Constant Volume

 

 

 

 

IAQ

Ð

Indoor Air Quality

 

 

 

 

OAT

Ð

Outdoor Air Temperature

 

 

 

 

39

Page 39