Carrier 50EW, 50EY, 50EK installation instructions Ð Base Unit Dimensions, 50EJ/EK024-034

Models: 50EK 50EY 50EW 50EJ

1 56
Download 56 pages 61.69 Kb
Page 4
Image 4
Fig. 3 Ð Base Unit Dimensions, 50EJ/EK024-034

NOTES:

1. Weights include economizer (Std)

2. Manual background Center of gravity.

3. Do not locate adjacent units with dis- charge facing economizer inlet. Mini- mum clearances to be:

Adjacent Units: 15 -0

Top of Units: No overhang

Condenser Coil: 4 -0

Economizer Side: 6 -0

Filter Access Side: 10 -0 (for re- moval of evaporator coil)

4. For smaller service and operational clearances, contact Carrier Applica- tion Engineering department.

5. Bottom ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on accessory roof curb.

6. Dimensions are in inches. Dimen- sions in [ ] are in millimeters.

7. For units with electric heat, a ®eld- supplied 90° elbow must be installed in the supply ductwork below the unit discharge.