Carrier 50EJ, 50EW Notice To Riggers All Panels Must Be In Place, When Rigging, Ð Rigging Label

Models: 50EK 50EY 50EW 50EJ

1 56
Download 56 pages 61.69 Kb
Page 8
Image 8
NOTICE TO RIGGERS:

Step 2 Ð Rig and Place Unit Ð Inspect unit for trans- portation damage. File any claim with transportation agency. Keep unit upright, and do not drop. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is shown in Fig. 1 and 2. See Fig. 7 for additional information. Unit weight is shown in Table 1.

NOTE: On retro®t jobs, ductwork may be attached to old unit instead of roof curb. Be careful not to damage ductwork when removing unit. Attach existing ductwork to roof curb instead of unit.

Four lifting lugs are provided on the unit base rails as shown in Fig. 7. Refer to rigging instructions on unit.

POSITIONING Ð Provide clearance around and above unit for air¯ow, safety, and service access (Fig. 3-6).

Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

NOTICE TO RIGGERS:

ALL PANELS MUST BE IN PLACE

WHEN RIGGING.

NOTE: Rig with four cables and spread with two 92 in. (2337 mm) spreader bars. Maintain a dis- tance of 74 in. (1880 mm) from top of unit to eyehook.

NOTE:

Add 32 lb (14.5 kg) for domestic crating.

Add 312 lb (142 kg) for export crating (024-034 units). Add 346 lb (157 kg) for export crating (038-048 units). Add 250 lb (113 kg) for power exhaust.

Add 220 lb (100 kg) for copper condenser coil (024-034 units). Add 285 lb (129 kg) for copper condenser coil (038-044 units). Add 380 lb (172 kg) for copper condenser coil (048 unit).

MODEL

WEIGHT

 

A

 

B

 

C

50EJ/EK/EW/EY

lb

kg

in.

 

mm

in.

 

mm

in.

 

mm

024

4016

1822

87.68

 

2227

71.4

 

1814

41.7

 

1059

028

 

 

 

 

 

 

 

 

 

 

 

030

4102

1860

87.68

 

2227

68.5

 

1740

43.6

 

1107

034

 

 

 

 

 

 

 

 

 

 

 

038*

4282

1942

 

 

 

91.3

 

2319

46.5

 

1181

044

4508

2045

150

 

3810

87.8

 

2230

46.5

 

1181

048*

4795

2175

 

 

 

86.2

 

2189

46.1

 

1171

 

 

 

 

 

 

 

 

 

 

 

 

*Sizes 038 and 048 are 50EJ,EW units only.

Fig. 7 Ð Rigging Label

8

Page 8
Image 8
Carrier 50EJ, 50EW, 50EY, 50EK Notice To Riggers All Panels Must Be In Place, When Rigging, Ð Rigging Label