Carrier 50EY, 50EJ, 50EW, 50EK installation instructions Setting

Models: 50EK 50EY 50EW 50EJ

1 56
Download 56 pages 61.69 Kb
Page 34
Image 34

Table 10A Ð DIP Switch Con®guration (Version 1.0 of Unit Control Software)

SETTING

1

2

3

4

5

6

7

8

OPEN

 

CCN/

Expansion

Field

Modulated

Time Guard Override

 

 

VAV

Test

Power

ON/ Set Min.

Gas Heat

Factory Test ON

Sensors

I/O Board

 

 

ON

Exhaust

Damper Pos. ON

 

 

 

 

 

 

 

 

CLOSED

 

 

Base Board

Field

CV

Time Guard Override

 

 

CV

TSTAT

Test

Power

OFF/ Set Min.

Electric Heat

Factory Test OFF

Only

 

 

 

OFF

Exhaust

Damper Pos. OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

CCN

Ð Carrier Comfort Network

CV

Ð Constant Volume

I/O

Ð

Input/Output

POS.

Ð

Position

TSTAT

Ð Thermostat

VAV

Ð Variable Air Volume

NOTES:

1.The Factory Test DIP switch should not be enabled in the ®eld.

2.The OPEN side of the DIP switch is marked ``OPEN.'' When the rocker switch is on the ``OPEN'' side of the switch, the switch is open.

3.If DIP switch no. 1 is open, DIP switch no. 2 is ignored, since VAV units control to supply-air temperature.

Table 10B Ð DIP Switch Con®guration (Version 2.0 of Unit Control Software)

SETTING

1

2

3

4

5

6

7

8

 

 

 

 

 

VAV Ð

 

 

 

 

 

VAV Ð Space Sensor

 

 

Occupied

Time Guard Override

 

 

 

 

Installed

 

 

Heat

ON

 

 

OPEN

VAV

 

Expansion

Field Test

Enabled

 

Gas Heat

Heat Pump

 

Board

ON

CV Ð

IN CONJUNCTION

Operation

 

 

 

 

 

 

CV Ð CCN or Sensors

 

 

Modulated

WITH FIELD TEST

 

 

 

 

Used

 

 

Power

Ð Set Minimum

 

 

 

 

 

 

 

Exhaust

Damper Position

 

 

 

 

 

 

 

VAV Ð

 

 

 

 

 

VAV Ð No Space Sensor

 

 

Occupied

 

 

 

 

 

 

 

Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Base Control

Field Test

Disabled

Time Guard Override

 

Air Conditioner

CLOSED

CV

 

CV Ð

Electric Heat

 

Board Only

OFF

OFF

Operation

 

 

 

Constant

 

 

 

 

 

 

 

 

 

 

 

CV Ð Thermostat

 

 

Volume

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

Exhaust

 

 

 

LEGEND

CCN Ð Carrier Comfort Network

CV Ð Constant Volume

VAV Ð Variable Air Volume

NOTES:

1.The OPEN side of the DIP switch is marked ``OPEN.'' When the rocker switch is on the ``OPEN'' side of the switch, the switch is OPEN.

2.The con®guration of DIP switches 2 and 5 are dependent on DIP switch 1. If DIP switch 1 is set to OPEN (VAV operation), then DIP switches 2 and 5 will con®gure CV functions.

3.When the unit is ®eld-tested (DIP switch 4 to OPEN), the function of DIP switch 6 changes and it is used to set the minimum damper position.

Table 11A Ð DIP Switch Factory Settings (Version 1.0 of Unit Control Software)

UNIT

1

2

3

4

5

6

7

8

50EJ/EW

Closed

Closed

Closed

Closed

Closed

Closed

Closed

Closed

50EK/EY

Open

Closed

Closed

Closed

Open

Closed

Closed

Closed

 

 

 

 

 

 

 

 

 

Table 11B Ð DIP Switch Factory Settings (Version 2.0 of Unit Control Software)

UNIT

1

2

3

4

5

6

7

8

50EJ/EW

Closed

Closed

Closed

Closed

Closed

Closed

Closed

Closed

50EK/EY

Open

Closed

Closed

Closed

Closed

Closed

Closed

Closed

34

Page 34
Image 34
Carrier 50EY, 50EJ, 50EW, 50EK installation instructions Setting