50TC
(typically WHT) to the unit’s
CCN Bus |
|
|
|
| TB1 | PL | |
+ (RED) | 12 |
| |
|
TB1
GND (WHT) 14
TB1
– (BLK) 16
C08276
Fig. 51 - PremierLink CCN Bus Connections
ECONOMIZER SYSTEMS
The 50TC units may be equipped with a
Both economizers use
ECONOMI$ER IV
CONTROLLER
WIRING | OUTSIDE AIR | |
TEMPERATURE SENSOR | ||
HARNESS | ||
LOW AMBIENT | ||
| ||
ACTUATOR | SENSOR | |
|
C06021
Fig. 52 - EconoMi$er IV Component Locations
| OUTDOOR | |
| AIR HOOD | |
ECONOMI$ER2 | HOOD | |
PLUG | ||
SHIPPING | ||
| BRACKET |
GEAR DRIVEN
BAROMETRICDAMPER RELIEF
DAMPER
C06022
Fig. 53 - EconoMi$er2 Component Locations
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
8 |
7 |
LEGEND | Potentiometer Defaults Settings: | NOTES: | |||
DCV— Demand Controlled Ventilation | Power Exhaust | Middle | 1. | 620 ohm, 1 watt 5% resistor should be removed only when using differential | |
Minimum Pos. | Fully Closed |
| enthalpy or dry bulb. | ||
IAQ — Indoor Air Quality |
| ||||
DCV Max. | Middle | 2. | If a separate | ||
LA — Low Ambient Lockout Device | |||||
OAT — | DCV Set | Middle |
| supply, it cannot have the secondary of the transformer grounded. | |
POT— Potentiometer | Enthalpy | C Setting | 3. | For | |
RAT — |
|
|
| between P and P1 and set control minimum position POT to the minimum | |
|
|
|
| position. |
C06028
Fig. 54 - EconoMi$er IV Wiring
32