Carrier 50TCA04-A07 EconoMi$er2 with 4 to 20 mA Control Wiring, EconoMi$er IV Input/Output Logic

Models: 50TCA04-A07

1 73
Download 73 pages 19.81 Kb
Page 33
Image 33
Fig. 55 - EconoMi$er2 with 4 to 20 mA Control Wiring

500 OHM RESISTOR

NOTE 1

Table 11 – EconoMi$er IV Input/Output Logic RUN

NOTE 3

50HJ540573

ACTUATOR ASSEMBLY

DIRECT DRIVE

ACTUATOR

 

 

BLACK

4

TRANSFORMER

 

 

 

 

 

 

 

GROUND

 

 

 

3

 

 

 

 

5

 

 

 

BLUE

2

 

 

 

 

 

 

 

 

8

 

VIOLET

 

 

6

 

 

 

 

 

PINK

 

 

7

 

 

 

 

 

OAT SENSOR

 

RED

1

24 VAC

 

 

 

 

 

 

 

 

10

 

 

YELLOW

 

11

 

 

 

9

 

 

 

 

 

 

 

WHITE

 

4-20 mA

4-20mA SIGNAL

 

12

TO J9 ON

 

 

 

 

 

PremierLink

 

 

 

 

 

 

 

 

BOARD

 

 

ECONOMISER2 PLUG

50TC

NOTES:

1.Switch on actuator must be in run position for economizer to operate.

2.PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen sor or HH57A077 enthalpy sensor.

3.50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

C08310

Fig. 55 - EconoMi$er2 with 4 to 20 mA Control Wiring

Table 11 – EconoMi$er IV Input/Output Logic

 

INPUTS

 

 

 

 

 

OUTPUTS

 

Demand Control

Enthalpy*

 

 

 

Compressor

N Terminal†

 

 

Y1

Y2

Stage

Stage

Occupied

Unoccupied

Ventilation (DCV)

Outdoor

Return

 

 

1

2

Damper

 

 

 

 

 

 

High

 

On

On

On

On

 

 

 

Low

On

Off

On

Off

Minimum position

Closed

 

(Free Cooling LED Off)

Below set

 

Off

Off

Off

Off

 

 

 

 

 

 

(DCV LED Off)

Low

 

On

On

On

Off

Modulating** (between min.

Modulating** (between

 

High

On

Off

Off

Off

position and full-open)

closed and full-open)

 

(Free Cooling LED On)

 

 

Off

Off

Off

Off

Minimum position

Closed

 

 

 

 

High

 

On

On

On

On

Modulating†† (between min.

Modulating†† (between

 

Low

On

Off

On

Off

position and DCV

closed and DCV

 

(Free Cooling LED Off)

 

 

 

 

 

 

maximum)

maximum)

Above set

 

Off

Off

Off

Off

 

 

(DCV LED On)

 

 

 

 

 

 

 

 

Low

 

On

On

On

Off

 

 

 

High

On

Off

Off

Off

Modulating***

Modulating†††

 

(Free Cooling LED On)

 

 

Off

Off

Off

Off

 

 

 

 

 

 

 

*For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.

Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied). ** Modulation is based on the supply-air sensor signal.

†† Modulation is based on the DCV signal.

*** Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal).

††† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-air signal).