Carrier 50TCA04-A07 appendix Ton Horizontal Supply, Ton Vertical Supply, 50TC**07, Phase

Models: 50TCA04-A07

1 73
Download 73 pages 19.81 Kb
Page 61
Image 61
50TC**07

APPENDIX III. FAN PERFORMANCE (cont.)

50TC**07

3

Phase

6 Ton Horizontal Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

 

 

 

CFM

 

 

 

0.2

 

0.4

 

0.6

0.8

 

 

1.0

 

RPM

BHP

RPM

BHP

RPM

 

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

Field Supplied Drive1

 

 

 

 

Standard Static Option

 

 

 

1800

 

822

 

0.51

927

0.66

1018

0.82

1100

0.98

1174

1.15

1950

 

872

 

0.62

973

0.79

1061

0.95

1140

1.13

1213

1.31

2100

 

923

 

0.75

1019

0.92

 

 

1.10

1182

1.29

1253

1.48

 

 

1104

 

2250

 

974

 

0.90

1067

1.08

1149

1.27

1224

1.46

1294

1.66

2400

 

1026

1.06

 

 

1195

1.46

1268

1.66

1336

1.87

 

1115

1.26

2550

 

1079

 

1.25

1164

1.46

1241

1.67

1312

1.88

1379

2.10

2700

 

1132

 

1.46

1214

1.67

1289

1.90

1358

2.12

1422

2.35

2850

 

1186

 

1.69

1264

1.92

1336

2.15

1404

2.39

 

 

 

 

1467

2.63

3000

 

1240

 

1.94

1315

2.18

1385

 

2.43

1451

2.68

1512

2.93

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

 

 

 

CFM

 

 

 

1.2

 

1.4

 

1.6

1.8

 

 

2.0

 

RPM

BHP

RPM

BHP

RPM

 

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

Standard Static Option

 

 

Medium Static Option

1800

 

1244

 

1.33

1308

1.51

1369

1.70

1427

1.90

1483

2.10

1950

 

1281

 

1.49

1345

1.68

1405

1.88

1462

2.09

1517

2.30

2100

 

1320

 

1.67

1382

1.87

1441

2.08

1498

2.29

1552

2.51

2250

 

1359

 

1.87

1420

2.08

 

 

2.29

1534

2.51

1587

2.74

 

 

1479

 

2400

 

1400

 

2.09

1460

2.31

1517

2.53

1572

2.76

1624

2.99

2550

 

1441

 

2.33

1500

2.55

1557

2.79

1610

3.03

1662

3.27

2700

 

1483

 

2.59

1541

2.83

1597

 

3.07

1650

3.32

1701

3.57

2850

 

1527

 

2.87

1583

3.12

1638

3.37

1690

3.63

---

---

3000

 

1571

 

3.18

1626

3.44

1680

3.70

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 543.

Boldface indicates field--- supplied drive is required.

1.Recommend using field--- supplied fan pulley (part number KR11AZ406), motor pulley (part number KR11HY151) and belt (part number KR30AE035).

50TC**07

3 Phase

6 Ton Vertical Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

 

 

 

CFM

 

 

0.2

 

0.4

 

0.6

0.8

 

1.0

 

 

RPM

BHP

RPM

BHP

RPM

 

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

Field Supplied Drive1

 

 

 

 

Standard Static Option

 

 

 

1800

 

907

0.63

1006

0.80

1092

0.97

1169

1.14

1239

1.32

1950

 

965

0.77

1060

0.95

1143

 

1.13

1218

1.32

1287

1.51

2100

 

1024

0.93

1115

1.12

1195

1.32

1268

1.52

1335

1.72

2250

 

1083

1.11

1170

1.32

1248

1.53

1319

1.74

1385

1.96

2400

 

1143

1.32

1227

1.54

1302

1.76

1371

1.99

1435

2.22

2550

 

1203

1.55

1284

1.78

1357

2.02

1424

2.26

 

 

 

1487

2.50

2700

 

1264

1.81

1342

2.06

1412

2.31

1478

2.56

1539

2.82

2850

 

1326

2.09

1400

2.36

1469

 

2.62

1532

2.89

1592

3.16

3000

 

1387

2.41

1459

2.69

1525

2.97

1587

3.25

1646

3.53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

 

 

 

CFM

 

 

1.2

 

1.4

 

1.6

1.8

 

2.0

 

 

RPM

BHP

RPM

BHP

RPM

 

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

Standard Static Option

 

 

 

Medium Static Option

 

1800

 

1304

1.51

1365

1.69

1422

1.88

1477

2.08

1528

2.28

1950

 

1350

1.71

1410

1.91

1467

 

2.11

1520

2.31

1572

2.52

2100

 

1398

1.93

1457

2.14

1512

2.35

1565

2.57

1616

2.79

2250

 

1446

2.18

 

 

1559

2.62

1611

2.85

 

 

 

1504

2.40

1661

3.09

2400

 

1496

2.45

1552

2.68

1606

 

2.92

1658

3.16

1707

3.40

2550

 

1546

2.75

1601

2.99

1654

3.24

1705

3.50

---

---

2700

 

1597

3.07

1651

3.33

1703

3.59

---

---

---

---

2850

 

1648

3.43

1702

3.70

---

 

---

---

---

---

---

3000

 

---

---

---

---

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 54.

Boldface indicates field--- supplied drive is required.

1.Recommend using field--- supplied fan pulley (part number KR11AZ406), motor pulley (part number KR11HY151) and belt (part number KR30AE035).

50TC

61

Page 61
Image 61
Carrier 50TCA04-A07 Ton Horizontal Supply, Ton Vertical Supply, 50TC**07, APPENDIX III. FAN PERFORMANCE cont, Phase