Fig. 56 - EconoMi$er IV Functional View
EconoMi$er IV
Table 11 provides a summary of Economizer IV. Troubleshooting instructions are enclosed.
A functional view of the EconoMi$er is shown in 56. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is available from Carrier to help with EconoMi$er IV training and troubleshooting.
EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. (See Fig. 57.) This sensor is factory installed. The operating range of temperature measurement is 0° to 158_F
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
C06033
Fig. 57 - Supply Air Sensor Location
The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Outdoor Air Lockout Sensor
The EconoMi$er IV is equipped with an ambient temperature lockout switch located in the outdoor airstream which is used to lock out the compressors below a 42_F (6_C) ambient temperature. (See Fig. 52.)
EconoMi$er IV Control Modes
IMPORTANT: The optional EconoMi$er2 does not include a controller. The EconoMi$er2 is operated by a 4 to 20 mA signal from an existing
Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. (See Table 12.) The EconoMi$er IV is supplied from the factory with a
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable setpoint selected on the control. If the