Table 16 – Torque Values

Table 16 – Torque Values

Supply fan motor mounting

120

+/

---

12 in---

lbs

Supply fan motor adjustment plate

120

+/

---

12 in---

lbs

Motor pulley setscrew

72+/---

5 in---

lbs

 

Fan pulley setscrew

72+/---

5 in---

lbs

 

Blower wheel hub setscrew

72+/---

5 in---

lbs

 

Bearing locking collar setscrew

65---

70 in

--- lbs

 

Compressor mounting bolts

65---

75 in

--- lbs

 

Condenser fan motor mounting bolts

20 +/---

2 in---

lbs

Condenser fan hub setscrew

84 +/---

12 in

--- lbs

50TC

C08393

Fig. 65 - 50TC Typical Unit Wiring diagram - Power (A06)