Carrier 50TCA04-A07 appendix PremierLink Sensor Usage, Application

Models: 50TCA04-A07

1 73
Download 73 pages 19.81 Kb
Page 26
Image 26
Table 6 – PremierLink Sensor Usage

50TC

Table 6 – PremierLink Sensor Usage

 

 

 

 

 

 

 

 

 

 

OUTDOOR AIR

RETURN AIR

OUTDOOR AIR

RETURN AIR

APPLICATION

TEMPERATURE

TEMPERATURE

ENTHALPY SENSOR

ENTHALPY SENSOR

 

 

 

SENSOR

SENSOR

 

 

 

 

 

 

 

 

 

 

Differential Dry Bulb

 

Required ---

 

 

Temperature with

Included ---

 

 

PremierLink (PremierLink

33ZCT55SPT

---

---

CRTEMPSN001A00

requires 4--- 20 mA

or equivalent

 

 

 

 

 

Actuator)

 

 

 

 

 

 

 

 

 

 

Single Enthalpy with

Included ---

 

Requires ---

 

PremierLink (PremierLink

 

 

---

HH57AC077

---

requires 4--- 20mA

Not Used

 

or equivalent

 

Actuator)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Differential Enthalpy with

Included ---

 

Requires ---

Requires ---

PremierLink (PremierLink

 

---

HH57AC077

HH57AC078

requires 4--- 20mA

Not Used

 

or equivalent

or equivalent

Actuator)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

CO2 Sensors (Optional):

 

 

 

 

33ZCSENCO2

---

Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.

 

33ZCASPC02

---

Aspirator box used for duct--- mounted CO2 room sensor.

 

 

33ZCT55CO2

---

Space temperature and CO2 room sensor with override.

 

 

33ZCT56C02

---

Space temperature and CO2 room sensor with override and setpoint.

 

26

Page 26
Image 26
Carrier 50TCA04-A07 appendix PremierLink Sensor Usage, Application