To Use Cooling Charging Charts

To Use Cooling Charging Charts

Take the outdoor ambient temperature and read the suction pressure gauge. Refer to chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.

EXAMPLE: Model 50TC*A06

Outdoor Temperature . . . . . . . . . . . . . . . . . . 85_F (29_C) Suction Pressure . . . . . . . . . . . . . . . . . 130 psig (896 kPa) Suction Temperature should be . . . . . . . . . 63_F (17.2_C)

50TC

SEAT 1/2-20 UNF RH

0.596

Fig. 11 - CoreMax Access Port Assembly30o

WASHER

45o

DEPRESSOR PER ARI 720 +.01/-.035

5/8” HEX

.47

1/2" HEX

FROM FACE OF BODY

O-RING

This surface provides a metal to metal seal when torqued into the seat. Appropriate handling is required to not scratch or dent the surface.

SEAT

CORE

Fig. 11 - CoreMax Access Port Assembly

7/16-20 UNF RH

C07150

8

Page 8